Rated output
T
V/
T
R
= 40/30 °C
kW
187
248
314
408
508
635
T
V
/T
R
= 80/60 °C
kW
170
225
285
370
460
575
Rated thermal load
kW
177
234.5
297
385.5
479
599
Product ID
CE-0085 AQ 0257
Flue gas parameters
Temperature (at return
temp. 30 °C)
&
at rated output
°C
45
45
45
45
45
45
&
at partial load
°C
40
40
40
40
40
40
Temperature (at return
temp. 60 °C)
°C
75
75
75
75
75
75
Product parameters
(according to EnEV)
Efficiency
η
&
at 100 % of rated
output
%
97.6
97.6
97.8
97.5
97.6
97.6
&
at 60% of rated out-
put
%
107.5
108.2
108.2
107.2
107.5
107.3
Standby loss
q
B,70
%
0.4
0.3
0.3
0.3
0.28
0.25
Power consump-
tion
*
1
&
at 100 % of rated
output
W
529
606
678
769
854
950
&
at 60% of rated out-
put
W
176
202
226
256
285
317
Water quality requirements
Note
Maintaining the following requirements is necessary to safeguard your warranty
rights.
The manufacturer's warranty excludes damage due to corrosion and scaling.
Specification
29
Specification
56
92
405
GB
*1
Standard characteristics
Summary of Contents for VITOCROSSAL 300
Page 22: ...Parts lists cont 22 Parts lists 5692 405 GB ...
Page 23: ...Parts lists cont 23 Parts lists 5692 405 GB ...
Page 24: ...Parts lists cont 24 Parts lists 5692 405 GB ...
Page 25: ...Parts lists cont 25 Parts lists 5692 405 GB ...
Page 26: ...Parts lists cont 26 Parts lists 5692 405 GB ...
Page 27: ...Parts lists cont 27 Parts lists 5692 405 GB ...
Page 35: ...35 5692 405 GB ...