Vitocell 100-VH/-BH Technical Data

Sensor well

The stainless steel sensor wells are to be used for control 
sensors to ensure maximum operational safety. The top 
sensor well is used for the DHW sensor connected to the 
boiler control.

For solar heating systems, Viessmann recommends 
placement of the DHW tank temperature sensor in the solar 
collector return.

Heating water supply temperature over 230º F (110ºC).

These operating conditions require the installation of an 
additional safety high limit into the DHW storage tank, 
preventing the temperature from rising above 203ºF
(95ºC). 

A domestic hot water tempering valve must be used.

System Design

WARNING

To ensure optimum, safe operation, the stainless steel 
well must be installed. The well diameter is large 
enough to accommodate a wide variety of sensing 
bulbs. 
Always use spring clip to ensure proper contact of 
capillary bulb against the stainless steel well for proper 
sensing/heat transfer!

Temperature and pressure relief valve

The heating contractor must install a temperature and 
pressure relief valve (T&P relief valve) on each tank in a 
method meeting code requirements. If local codes require 
a different relief valve, substitute the manufacturer’s 
supplied valve. The tank is approved for 100 psig where a 
CRN is required. Maximum operating pressure is 150 psig. 
Maximum operating temperature is 

210º F (99º C).

The T&P relief valve must be tested under ANSI Z21.22 
Code for Relief Valves and Automatic Gas Shut-off Devices 
for Hot Water Supply Systems. 

Backflow preventers

Where backflow preventers are required, a domestic water 
expansion tank installation must be installed in the cold 
water inlet piping before the cold water enters the Vitocell. 
For the backflow device, observe local plumbing codes and 
regulations.

Electric heating element 

4.5 kW

The optional screw-in electric heating element is used 
in enameled solar and domestic water storage tanks as 
auxiliary or emergency heating.  It should be mounted in 
a horizontal position by heating contractor.

 System Design

WARNING

To avoid damage to the screw head and/or heating 
element, do not operate the heating element without 
a medium.

WARNING

Ensure the heating element ground wire is securely 
connected to ground.

WARNING

Do not operate the heating element without a medium. 
Damage to the heating element and screw head may 
occur if operated without a medium.

IMPORTANT

Summary of Contents for VITOCELL 100-BH

Page 1: ...e Price List NCVA and NCVB Series Indirect fired domestic hot water storage tank with one or two heat exchanger coils With or without an optional electric heating element Storage capacity 79 USG 300 L 119 USG 450 L VITOCELLr 100 VH BH Product may not be exactly as shown ...

Page 2: ...andby losses minimized by highly effective 2 in 50 mm foamed in place CFC free insulation Thermometer included Sensor tube included Fitted with 1b in sleeve for re fitting of an electric heating inspection opening All external threads are flat sealing CFC free soft PU foam insulation with a thickness of 2 in 50 mm and a PVC coating Bottom insulation included in accordance with DIN 4753 Part 8 Comp...

Page 3: ...W connection J Magnesium Anode or impressed current anode K Thermometer option L Electric heater option M Inspection maintenance opening N Ground connection Connections Vitocell 100 VH NCVA 79 USG 300 L Vitocell 100 VH NCVA 119 USG 450 L Vitocell 100 BH NCVB 79 USG 300 L Vitocell 100 BH NCVB 119 USG 450 L A male 1 in 1a in 1 in 1a in B male 1 in 1 in 1 in 1 in D male 1 in 1 in 1 in 1 in E male 1 i...

Page 4: ...0 Max Operating Pressure Domestic water psi bar 150 10 34 150 10 34 150 10 34 150 10 34 Heating Circuit psi bar 230 16 230 16 230 16 230 16 Solar Circuit psi bar 230 16 230 16 230 16 230 16 Test Pressure Domestic water psi bar 300 20 7 300 20 7 300 20 7 300 20 7 Heating Circuit psi bar 300 20 7 300 20 7 Solar Circuit psi bar 300 20 7 300 20 7 300 20 7 300 20 7 Max Operating Temp Warmwater F C 210 ...

Page 5: ...rking pressure on DHW water side of up to 150 psig at 210 F 99 C max testing pressure on DHW side of 300 psig Model Vitocell 100 VH NCVA Vitocell 100 VH NCVA Storage Capacity USG L 79 2 300 119 450 Coil Lower 1 Lower 1 Recovery Rate 2 with a DHW temperature increase from 50º F to 113º F 10º C to 45º C and a supply water temperature of 90 C MBH kW GPH L h 181 52 92 343 4 1300 239 70 01 454 4 1720 8...

Page 6: ...00 BH NCVB Vitocell 100 BH NCVB Storage Capacity USG L 79 2 300 119 450 Coil Upper 1 Lower 2 Upper 1 Lower 2 Recovery Rate 3 with a DHW temperature increase from 50º F to 113º F 10º C to 45º C and a supply water temperature of 90 C MBH kW GPH L h 110 32 36 210 0 795 181 52 92 343 4 1300 142 41 76 271 0 1026 239 70 01 454 4 1720 80 C MBH kW GPH L h 92 26 87 174 4 660 150 43 96 285 3 1080 118 34 60 ...

Page 7: ... v1 1Vitocell 100 VH BH Technical Data Specifications Flow Rate A Lower coil 119 USG 450 L capacity B 79 USG 300 L Lower coil and 119 USG 450 L Upper coil C 79 USG 300 L Upper coil A 79 USG 300 L B 119 USG 450 L ...

Page 8: ...8 5470 954 v1 1 Vitocell 100 VH BH Technical Data Specifications Dimensions Vitocell 100 VH NCVA Vitocell 100 VH NCVA Vitocell 100 BH NCVB Vitocell 100 BH NCVB ...

Page 9: ...alve PR Pressure reducing valve D Drain DCW Cold water supply lines PGC Pressure gage connection E Precharged expansion tank required where backflow preventer is installed check local plumbing codes and requirements BP1 Backflow preventer BP2 Backflow preventer T P Temperature and pressure relief valve DW Water filter DHW Domestic hot water supply RP Recirculation pipe RPU Recirculation pump Heati...

Page 10: ...esign Legend A Solar collector B Vitocell 100 C Filling valve D Solar Divicon pumping station E Recirculating pump F Anti scald tempering valve HC Heating circuit B Oil Gas fired boiler DCW Domestic cold water DHW Domestic hot water T P Temperature and pressure relief valve Solar connection ...

Page 11: ... tank in a method meeting code requirements If local codes require a different relief valve substitute the manufacturer s supplied valve The tank is approved for 100 psig where a CRN is required Maximum operating pressure is 150 psig Maximum operating temperature is 210º F 99º C The T P relief valve must be tested under ANSI Z21 22 Code for Relief Valves and Automatic Gas Shut off Devices for Hot ...

Page 12: ...12 5470 954 v1 1 Technical information subject to change without notice Printed on environmentally friendly recycled and recyclable paper Vitocell 100 VH BH Technical Data ...

Reviews: