109
Coding in the delivered condition
Possible change
Vacuum module delay
2D:10
Delay of the vacuum module
10 seconds
2D:1
to
2D:250
Setting range in seconds
Changeover unit
64:4
The changeover unit has
4
probes.
Code available if changeover unit
type 0 is connected.
64:1
to
64:8
Setting range:
1
probe to
8
probes
Changeover unit, runtime
65:90
Runtime of the changeover unit
90 minutes. Code available if
changeover unit type 0 is connec-
ted.
65:5
to
65:120
Setting range in minutes
Changeover unit, backwashing runtime
66:0
Backwashing runtime for the
changeover unit 0 seconds. Code
available if changeover unit type 0
is connected.
66:0
to
66:30
Setting range in minutes
Transverse screw conveyor, light barrier delay
C0:...
The light barrier delay of the trans-
verse screw conveyor delays dis-
charge by 5 seconds.
C0:5
to
C0:100
Setting range in minutes
Proximity switch, pellet hopper
E8:0
Pellet hopper proximity switch only
for detecting the maximum fill level
in the pellet hopper.
E8:1
Pellet flow detection (replacement
pellet flow sensor).
Heating
Coding
Coding in the delivered condition
Possible change
DHW priority
A2:0
No priority control during cylinder
heating
Note
Individually adjustable for each
heating circuit.
Select heating circuit with
Á
.
A2:1
During cylinder heating, the mixer
closes. If the heating circuit is wired
to the boiler control unit, the heating
circuit pump remains switched on. If
an extension kit is used for the heat-
ing circuit, the heating circuit pump
is switched off.
A2:2
During cylinder heating, the mixer is
closed and the heating circuit pump
is switched off.
A2:3
During cylinder heating, the set val-
ue for the flow temperature is adjus-
ted to the set value for reduced
heating mode.
Frost protection temperature
A3:2
Outside temperature below 1 °C:
Frost protection function
"On"
Outside temperature above 3 °C:
Frost protection function
"Off"
A3:-9
to
A3:15
Frost protection function
"On"
/
"Off"
See the following table:
Codes
Code 2
(cont.)