Technical Data
39½” /
19¾” /
500 mm
19¾” /
500 mm
8” / 200 mm
d
c
1000 mm
VITOROND 200, VD2
9
Recommended Minimum Service Clearances
The combustion chamber door is factory assembled to hinge on the left-hand
side. A right-hand hinge is feasible by rebuilding the door hinge hardware.
Boiler model
VD2-125
VD2-160
VD2-195
VD2-230
VD2-270
c
inches
mm
47¼
1200
53
1350
59
1500
65
1650
71
1800
d
inches
mm
Dependent on burner model
Inch dimensions rounded to the nearest ¼”.
Front clearances (dimension “c” above) will allow for easy removal of flue gas
turbulator inserts, as well as for full insertion of bristle brush for heat exchanger
cleaning.
Minimum side clearance of 19¾” / 500 mm
must be maintained for side-mounted KR or
Dekamatik controls.
Recommended Clearances to Combustibles
Boiler model
VD2-
125
160
195
230
270
Top
6” / 150 mm
Sides
6” / 150 mm
Flue (oil)
9” / 229 mm
Flue (gas)
6” / 150 mm
Front
6” / 150 mm
Floor
non-combustible
Maintain 1” air clearance from uninsulated
hot water pipes to combustible material.
Boiler must not be installed on carpet.
5285
661
v1
.4
IMPORTANT
IMPORTANT
IMPORTANT