Technical Data
4
VITOROND 200, VD2
Technical data
*1
Boiler model
VD2-
125
160
195
230
270
Input (oil)
MBH
490
628
765
902
1059
kW
144
184
224
264
310
Input (gas)
MBH
508
650
792
934
1096
kW
149
190
232
274
321
Output (oil/gas)
MBH
432
553
673
794
932
kW
127
162
197
233
273
Combustion efficiency (oil)
%
88
88
88
88
88
Combustion efficiency (gas)
%
85
85
85
85
85
Number of cast iron sections
5
6
7
8
9
Cast iron block dimensions
Length
Width
Height
inches
mm
inches
mm
inches
mm
35¼
893
29¼
743
40
1015
40¼
1024
29¼
743
40
1015
45½
1155
29¼
743
40
1015
49½
1256
29¼
743
40
1015
55¾
1417
29¼
743
40
1015
Cast iron section dimensions
Front section (with combustion
chamber door)
Intermediate section
Rear section (with flue gas
collar)
inches
mm
inches
mm
inches
mm
32 x 29¼ x 10¼
810 x 743 x 261
32 x 24¾ x 5
810 x 628 x 130
32 x 24¾ x 9¼
810 x 628 x 238
Dimensions (with insul. jacket)
Total length
Total width with NR2 control
(side-mounted)
Total width with Dekamatik
(side-mounted)
Total width with KR control
(side-mounted)
inches
mm
inches
mm
inches
mm
inches
mm
41½
1056
39
990
42¾
1090
44¾
1140
46¾
1187
39
990
42¾
1090
44¾
1140
52
1318
39
990
42¾
1090
44¾
1140
57
1449
39
990
42¾
1090
44¾
1140
62¼
1580
39
990
42¾
1090
44¾
1140
Weight
Front section (with combustion
chamber door)
Intermediate section
Rear section (with flue gas
collar)
Cast iron heat exchanger block
Overall weight
complete with insulation
lbs
kg
lbs
kg
lbs
kg
lbs
kg
lbs
kg
309
140
203
92
256
116
1347
611
1424
646
309
140
203
92
256
116
1556
706
1624
745
309
140
203
92
256
116
1750
794
1845
837
309
140
203
92
256
116
1940
880
2044
927
309
140
203
92
256
116
2052
931
2196
996
Boiler water content
USG
ltr
20.6
78
24.0
91
27.5
104
30.9
117
34.3
130
Max. boiler temperature
*2
(= fixed high limit)
°F
°C
248
120
248
120
248
120
248
120
248
120
5285
661
v1
.4