System Design Considerations/Burner Alternatives

14

VITOROND 200, VD2

System Design Considerations

(continued)

/Burner Alternatives

Water quality

Treatment for boiler feed water should be
considered in areas of known problems,

such as where a high mineral content and
hardness exist. In areas where freezing

might occur, an antifreeze may be added to
the system water to protect the system.

Please adhere to the specifications given by
the antifreeze manufacturer. Do not use

automotive silicate-based antifreeze. Please
observe that an antifreeze/water mixture

may require a backflow preventer within the
automatic water feed and influence
components such as diaphragm expansion

tanks, radiation, etc. A 40% antifreeze
content will provide freeze-up protection to

-10°F / -23°C. Do

not

use antifreeze other

than specifically made for hot water heating

systems. System also may contain
components which might be negatively

affected by antifreeze. Check total system
frequently when filled with antifreeze.

Follow the instructions of antifreeze
manufacturer.

Oxygen diffusion barrier

underfloor tubing

The boiler warranty does not cover leaks
resulting from corrosion caused by the use
of underfloor plastic tubing without an

oxygen diffusion barrier. Such systems must
have the tubing without oxygen diffusion

barrier separated from the boiler with a heat
exchanger. Viessmann recommends the use

of underfloor plastic tubing with an oxygen
diffusion barrier.

Burner manufacturer

Weishaupt or Riello

Burner/Gas train approval

Standard approvals are CSA (for Canada)
and UL (for U.S.). IRI and FM approved
equipment is also available - please inquire.

Electrical requirements

Weishaupt W Series burners are available in
120 VAC, single-phase, in a 60 Hz
configuration. L, G, and GL Series burners

listed below are available in 120 VAC single
phase, 208 VAC three-phase, 460 VAC

three-phase, or 575 VAC three-phase, all in
60 Hz configuration. It is generally

acceptable to use voltages within ten
percent of the supply voltage. Available

voltage inside boiler room must be provided
at time of order. Ensure appropriate

disconnect means and overcurrent
protection.

Natural gas pressure

Natural gas pressures and heating values as
provided by the gas utilities vary greatly
across North America. Select the
appropriate gas train accordingly. Low
pressure gas trains have a maximum input

of 14 ”w.c.; high pressure gas trains have a
maximum pressure of 5 psig. Minimum gas
pressures apply - please inquire. Gas
pressures and heating values at site must be
provided at time of order.

Factory prewired components

Custom factory prewiring by Viessmann
ensures optimal functionality, compliance
with regional requirements, and ease of
installation in the field. Pricing provided by

Viessmann includes all necessary hardware
items such as junction panel, burner power
supply, boiler door safety switch (where
necessary), and all essential pressure
switches, as well as interconnection with
conduit between control and burner.

Electrical drawings provided upon product
delivery.

Boiler/Burner start-up

Vitorond 200, VD2 boilers with Weishaupt
burners require start-up by Viessmann.
Please inquire to obtain details regarding the
necessary prerequisites of boiler/burner
start-up procedures.

To minimize delivery lead times, please
ensure that critical technical information is
provided at time of order. Viessmann will
not process an order without site-specific
information regarding available voltage and
gas pressure. In addition Viessmann
recommends that gas pressure information
be provided in writing by the local gas
utility.

5285

661

v1

.4

IMPORTANT

Summary of Contents for VD2-125

Page 1: ...D 200 Triple pass hot water heating boiler 490 to 1096 MBH 144 to 321 kW Vitorond 200 Oil Gas fired boiler sectional cast iron design with Eutectoplex heat transfer surface in triple pass design for operation with modulating water temperatures Heating input 490 to 1096 MBH 144 to 321 kW 5285 661 v1 4 01 2008 ...

Page 2: ...rther increase the level of operational reliability H Low emission combustion through triple pass design H Problem free transport into difficult to access boiler rooms due to sectional construction and low weight of individual sections H Simple quick assembly of the individual cast iron sections is achieved with a double groove seal fit system for the flue gas passageways The gasket seal is secure...

Page 3: ...remely effective Third Vitotronic 300 control Burner door 4 100 mm thick pass intelligent and easy to install insulation insulation operate and service Second Combustion Eutectoplex heat exchanger Low emission pass chamber surface constructed from burner homogeneous special gray cast iron 5285 661 v1 4 ...

Page 4: ...28 x 130 32 x 24 x 9 810 x 628 x 238 Dimensions with insul jacket Total length Total width with NR2 control side mounted Total width with Dekamatik side mounted Total width with KR control side mounted inches mm inches mm inches mm inches mm 41 1056 39 990 42 1090 44 1140 46 1187 39 990 42 1090 44 1140 52 1318 39 990 42 1090 44 1140 57 1449 39 990 42 1090 44 1140 62 1580 39 990 42 1090 44 1140 Wei...

Page 5: ...0 C 0 30 0 27 0 24 0 20 0 18 Vent pipe collar outer 7 in mm 8 200 8 200 8 200 8 200 8 200 Flue gas resistance w c 0 20 0 35 0 51 0 67 0 75 at upper end of rated input mbar 0 5 0 9 1 3 1 7 1 9 1 Inch dimensions are rounded to the nearest 2 The maximum supply operating temperature max adjustable high limit lies approx 27 F 15 C below the fixed high limit setting 3 May be less in some Canadian provin...

Page 6: ...the supplied burner dimensions Note For mounting burners with blast tube diameters of 150 mm 6 to 240 mm 9 the door insulation refractory material can be cut to the required size The blast tube must protrude from the thermal insulation on the boiler door 5285 661 v1 4 Length Total length Total width Width Height Total height SG BD BWR BWS CO FGC CO 8 205 mm 600 mm 33 850 mm 23 42 1075 mm 28 730 mm...

Page 7: ... Kit Standard Equipment consisting of boiler supply and return header Boiler supply header Low Temperature Protection Boiler model VD2 125 160 195 230 270 30 Boiler Flow Package Ø 1 1 1 100 Boiler Flow Package Ø 2 2 2 3 3 Low temperature protection packages from Viessmann are required for Rondomat boilers A 30 Boiler Flow Package is typically utilized in single boiler installations 100 Boiler Flow...

Page 8: ...n of sensor installed in stainless steel well All boiler piping field supplied 100 Boiler Flow Package The 100 boiler flow package consists of H 1 3 Way return water mixing valve 1 actuator 1 circulating pump Boiler pump 3 Way return water mixing valve Low water cut off standard equipment Location of sensor installed in stainless steel well All boiler piping field supplied It is essential that the...

Page 9: ...unded to the nearest Front clearances dimension c above will allow for easy removal of flue gas turbulator inserts as well as for full insertion of bristle brush for heat exchanger cleaning Minimum side clearance of 19 500 mm must be maintained for side mounted KR or Dekamatik controls Recommended Clearances to Combustibles Boiler model VD2 125 160 195 230 270 Top 6 150 mm Sides 6 150 mm Flue oil ...

Page 10: ...alves are required to properly balance the system Viessmann can supply TA Victaulic balancing valves upon request The balancing should be carried out by a certified balancing firm prior to boiler start up Please contact Viessmann for your closest certified balancing firm VD2 125 and VD2 160 VD2 195 VD2 230 and VD2 270 Recommended Flow Rates Boiler model VD2 125 160 195 230 270 20 F t 1 40 F t 11 C...

Page 11: ...temperatures Oil fired 140 F 60 C Gas fired 149 F 65 C The Viessmann Dekamatik or Vitotronic control system 2 Stage burner operation For operation with modulating boiler water temperatures first stage 60 of heating output For operation with elevated boiler water temperatures No minimum heating input applies Burner calibration site Modulating burner operation For elevated boiler water temperatures ...

Page 12: ...ditional safety control requirements etc are known before the product order is placed to determine proper burner selection and pricing Boiler Control Alternatives For single boiler installations Dekamatik D1 E Vitotronic 100 GC1 1 Vitotronic 300 GW2 1 Digital boiler control systems for modulating boiler water temperature or boiler setpoint control For multiple boiler installations Dekamatik D1 D2 ...

Page 13: ...g as the chimney for which the vent is sized For example a 14 chimney would require a 14 barometric draft regulator Do not size the barometric draft regulator to the breeching outlet of the boiler unless the chimney is also intended to be of that diameter The size of the flue gas outlet on the boiler does not automatically determine the horizontal breeching or the actual chimney diameter The chimn...

Page 14: ...120 VAC single phase in a 60 Hz configuration L G and GL Series burners listed below are available in 120 VAC single phase 208 VAC three phase 460 VAC three phase or 575 VAC three phase all in 60 Hz configuration It is generally acceptable to use voltages within ten percent of the supply voltage Available voltage inside boiler room must be provided at time of order Ensure appropriate disconnect me...

Page 15: ...rs Boiler model VD2 125 160 195 230 270 No 2 oil fired 1 stage Model F15 F20 n a No 2 oil fired 2 stage Model n a RL28 2 Natural gas fired 1 stage with assembled gas train Model G750 n a Propane gas fired 1 stage with assembled gas train Model G750 n a Natural gas fired 2 stage with assembled gas train Model n a G900 n a Propane gas fired 2 stage with assembled gas train Model n a G900 n a Natural...

Page 16: ...ufacturing Company U S Inc 45 Access Road Warwick Rhode Island 02886 USA Tel 401 732 0667 Fax 401 732 0590 www viessmann us com info viessmann us com 16 VITOROND 200 VD2 Printed on environmentally friendly recycled and recyclable paper Printed on environmentally friendly recycled and recyclable paper 5285 661 v1 4 Technical information subject to change without notice ...

Reviews: