67
Coding
Coding in the delivered condition
Possible change
System design
00:2
System version 1:
One heating circuit with-
out mixer (A1), with DHW
heating
00:2
to
00:10
For system schemes, see
the following table:
Value
address
00: ...
System
version
Description
2
1
One heating circuit without mixer A1 (heating circuit 1), with
DHW heating (code is adjusted automatically)
4
2
One heating circuit with mixer M2 (heating circuit 2), with
DHW heating
6
3, 4
One heating circuit without mixer A1 (heating circuit 1) and
one heating circuit with mixer M2 (heating circuit 2), with DHW
heating (code is adjusted automatically)
8
5
One heating circuit with mixer M2 (heating circuit 2) and one
heating circuit with mixer M3 (heating circuit 3), with DHW
heating
10
5
One heating circuit without mixer A1 (heating circuit 1), one
heating circuit with mixer M2 (heating circuit 2) and one heat-
ing circuit with mixer M3 (heating circuit 3), with DHW heating
(code is adjusted automatically)
Code 1
General
5412 755 GB
Service