GB
General notice (liability): the details of this technical documents serve for description. Consents regarding the availability of certain features or
regarding a certain purpose always require a special written agreement.
Right reserved to make technical changes!
Page 44 GB
Slide the enclosed plastic collar (D) over the defrost
water drain hose (B).
Guide the defrost water drain heater (A) completely
through the defrost water drain hose (B), and in this pro-
cess, for easier insertion, the defrost water drain hose (B)
must be pulled as much in a straight line as possible.
Guide the defrost water drain hose (B) through the bore
hole (G, ø 31 mm) in the cell wall (F) from the inside.
Lubricant can be used if necessary.
Connect the defrost water drain hose (B) to the drain
port (E) on the evaporator condensate tray.
Put the defrost water drain heater (A) into the siphon (C).
Push the siphon (C) from the inside onto the defrost wa-
ter drain. Guide the defrost water drain into the defrost
water tray.
Cover the cut-out (G) for the defrost water drain hose (B)
with the plastic collar (D).