68
Message
System characteristics
Cause
Measures
F.92
Function of affected exten-
sion in emergency mode
ADIO electronics module
communication error
Check connections on ADIO elec-
tronics module and connection to
HMU heat management unit.
F.100
Function of the connected
electronics module in emer-
gency mode
Voltage error PlusBus
Check the PlusBus connecting ca-
ble.
F.160
Control mode
No communication via
CAN BUS to connected
electronics module
Check HMU heat management unit
connections and connecting leads.
Reset device.
F.192/02F0
Fuel cell not operating
Not filled with distilled wa-
ter
Carry out fuel cell module commis-
sioning again.
F.193/02F1
Fuel cell not operating
Filling with distilled water
was not confirmed during
commissioning
Carry out fuel cell module commis-
sioning again.
F.194/02F2
Fuel cell not operating
Draining of distilled water
was not confirmed
Drain out distilled water again and
confirm draining.
F.195/12F0
No power generation
Combustion control CO
content outside tolerance
range
■
Check gas type setting, correct if
required.
■
Check the balanced flue system
for:
–
Flue gas recirculation
–
Leaks
■
Ingress of flue gas due to insuffi-
cient clearance from,
for example, the flue system of a
solid fuel boiler
If the fault recurs, notify Viessmann
Technical Service.
Note
Reset the message on the fuel cell
module programming unit.
Then switch the ON/OFF switch of
the fuel cell module OFF for ap-
prox. 10 s and ON again.
Troubleshooting
Message overview
(cont.)
5839343
Diagnosis
Summary of Contents for E00T
Page 8: ...8 14 Keyword index 95 Index Index cont 5839343 ...
Page 97: ...97 5839343 ...
Page 98: ...98 5839343 ...
Page 99: ...99 5839343 ...