Viessmann CS 2800 Operating Manual Download Page 9

GB

General notice (liability): the details of this technical documents serve for description. Consents regarding the availability of certain features or 
regarding a certain purpose always require a special written agreement.

Page No. 5237378-04 GB 

14.3 

                                               

Right reserved to make technical changes!

14.3  Trouble shooting (continued)

Cause

Short circuit in temperature sensor.

Temperature sensor broken,
coldroom temperature >50°.

High pressure Pressostat activated.

Coldroom standard temperature has
been exceeded or is too low.

Door contact switch is not connected.
Coldroom door has been open for
more than four minutes.

Remedy

Replace temperature sensor.

Replace temperature sensor.

Check condensor for contamination and clean if
necessary. Check to see if condensing ventilator
is running. Reduce ambient temperature.
The display remains on, but can be deleted pressing a 
button.

Check evaporator for contamination and clean if
necessary. Check evaporator for icing and initiate
manual defrosting if required. Check if evaporator
ventilator is running. By pressing the increase or
decrease button, coldroom temperature will be
shown again. If the temperature deviation is still
too high after one hour, the error code will be 
shown again.

Put sliding switch on the control panel into the
position without door contact switch. Close door.

Problem

Alarm light is flashing
Error Code F1 in display

Alarm light is flashing
Error Code F2 in display

Alarm light is flashing
Error Code F3 in display

Alarm light is flashing
Error Code F4 in display

Alarm light is flashing
Error Code F5 in display

Summary of Contents for CS 2800

Page 1: ...se read carefully the following prior to beginning work on the refrigeration unit Assembly maintenance cleaning and repair may only be Work on the refrigeration unit may only be carried out if the plu...

Page 2: ...5 Standards and regulations 6 Emergency operation 7 Defrosting 8 Serial interface 8 1 Door contact switch 9 Cleaning and maintenance of the refrigeration unit 10 Disposing of refrigerant 11 Control an...

Page 3: ...ng circulation system is opened by unauthorized personnel if there is interference in the system or if the serial number on the machine is changed or rendered unreadable 3 Area of installation The are...

Page 4: ...r source during cleaning and secure against reinsertion The cooling unit should be inspected periodically after beginning operation and if necessary cleaned Depending on requirements the intervals bet...

Page 5: ...perature The temperature setting is increased by pushing the button for at least three seconds A shorter push of the button shows the current coldroom temperature setting The temperature setting is de...

Page 6: ...efrosting time min is flashing By pressing the or the button the defrosting time can be increased or decreased by one minute at a time lt can be set between 5 and 60 minutes 13 2 3 Relative humidity L...

Page 7: ...he temperature sensor F2 Break in the temperature sensor During failure of temperature sens ons and a nominal temperature 2 C the compressor will continue to run with the last running and stand by set...

Page 8: ...ure is too high Suction and exhaust vents are blocked and the heat cannot be released Evaporator is dirty Condenser is dirty Door has been open too long Uncovered fluids are stored in the cell Defrost...

Page 9: ...for contamination and clean if necessary Check to see if condensing ventilator is running Reduce ambient temperature The display remains on but can be deleted pressing a button Check evaporator for co...

Page 10: ...85 Fresh poultry 1 1 85 90 Fresh venison 2 2 70 85 Fish Fish fresh from ice 0 1 90 100 Conserved fish 0 1 75 80 Milk and dairy products Milk 0 2 80 85 Butter 1 4 75 80 Soft cheese 0 2 80 85 Swiss che...

Page 11: ...notice liability the details of this technical documents serve for description Consents regarding the availability of certain features or regarding a certain purpose always require a special written...

Page 12: ...rtain features or regarding a certain purpose always require a special written agreement Page No 00044224 08 GB Viessmann K ltetechnik GmbH Schleizer Stra e 100 95030 Hof Saale Germany Phone 49 0 92 8...

Reviews: