Emergency operation

 
 

lf the regulator stops operating, the cooling unit can

 

continue to operate on an emergency basis. After removal

 

of the front panel, the regulator is accessible. By activating

 

the flip switch, the output for the compressor and the 

 

ventilators is bridged.The unit is then in permanent 

 

operation.The function of the pressostat as a safety device

 

is maintained.

 

 
  
 

 

Important!

 
 

 

 

Emergency operation must be monitored, since the 

 

coldroom temperature is not regulated.The coldroom 

 

temperature must be adjusted manually by switching 

 

of the power supply at intervals.

 

 
7. 

Defrosting

 
 

Automatic defrosting takes place automatically above +3°C.

8. 

Serial interface RS 232 

 
 

The regulator has a 9-pole D Sub plug on the back of the

 

plate. The serial interface serves as a connection to the

 

remote control supplied optionally and is prepared for 

 

connection to a central control unit.

8.1 

Door contact switch

 

lf the multiple pole plug of the unit is connected to a door

 

contact switch, the sliding switch on the regulator must be

 

placed in the position ‚with door contact switch. The switch

 

is accessible after removing the front cover.

9. 

Cleaning and maintenance of the refrigeration unit

 
 

     

 

 

   

Attention!

 

Remove plug from power source during cleaning and

 

secure against reinsertion.

 

-  The cooling unit should be inspected periodically after  

 

  beginning operation and, if necessary, cleaned. 

 

  Depending on requirements, the intervals between 

 

  inspection and cleaning have to be determined.The 

 

  cleaning intervals depend on the condition of the 

 

  surroundings.

 

-  The condenser and evaporator can be cleaned with a

 

  soft brush, compressed air or, in case of oil residues, 

 

  with a high pressure cleaner. Do not use any sharp or

 

  pointed objects. The fins should not be bent or 

 

  damaged during cleaning.

 

  By courtesy of intensive contamination with solvents or 

 

  outgasing synthetics natural discolorations can appear 

 

  on the SilverProtec surface. These are unproblematicly 

 

  removable with common purifiers based on oxygen or 

 

  with bleaching agents with a reaction time conforming 

 

  to the gravity of discoloration. The purifiers Vanish 

 

  Oxiaction from Hoffmanns or Sil OXIperfect from Henkel 

 

  perform well. Both products are available in trade. For 

 

  the cleaning of vertical areas on which the sprayed 

 

  purifier would slide down without a reaction time, we 

 

  recommend to spray the purifier on a cleaning rag and 

 

  then press it slightly on the discoloured spot so that the 

 

  rag doesn‘t slip off. Remove the rag after the reaction 

 

  time and wipe the treated spot again.

 

  Pay attention to the product information!

10. 

Disposing of refrigerant

 

lf the cooling unit has to be replaced by a new one, take 

 

care not to damage the pipes on the cooling unit, to  

 

ensure that no coolant is released.

 

Defective cooling units must be disposed of according

 

to environmental regulations and guidelines. 

without
Door Contact Switch
with

Electronic regulator control after removal of front 
cover.

Summary of Contents for CS 2800

Page 1: ...se read carefully the following prior to beginning work on the refrigeration unit Assembly maintenance cleaning and repair may only be Work on the refrigeration unit may only be carried out if the plu...

Page 2: ...5 Standards and regulations 6 Emergency operation 7 Defrosting 8 Serial interface 8 1 Door contact switch 9 Cleaning and maintenance of the refrigeration unit 10 Disposing of refrigerant 11 Control an...

Page 3: ...ng circulation system is opened by unauthorized personnel if there is interference in the system or if the serial number on the machine is changed or rendered unreadable 3 Area of installation The are...

Page 4: ...r source during cleaning and secure against reinsertion The cooling unit should be inspected periodically after beginning operation and if necessary cleaned Depending on requirements the intervals bet...

Page 5: ...perature The temperature setting is increased by pushing the button for at least three seconds A shorter push of the button shows the current coldroom temperature setting The temperature setting is de...

Page 6: ...efrosting time min is flashing By pressing the or the button the defrosting time can be increased or decreased by one minute at a time lt can be set between 5 and 60 minutes 13 2 3 Relative humidity L...

Page 7: ...he temperature sensor F2 Break in the temperature sensor During failure of temperature sens ons and a nominal temperature 2 C the compressor will continue to run with the last running and stand by set...

Page 8: ...ure is too high Suction and exhaust vents are blocked and the heat cannot be released Evaporator is dirty Condenser is dirty Door has been open too long Uncovered fluids are stored in the cell Defrost...

Page 9: ...for contamination and clean if necessary Check to see if condensing ventilator is running Reduce ambient temperature The display remains on but can be deleted pressing a button Check evaporator for co...

Page 10: ...85 Fresh poultry 1 1 85 90 Fresh venison 2 2 70 85 Fish Fish fresh from ice 0 1 90 100 Conserved fish 0 1 75 80 Milk and dairy products Milk 0 2 80 85 Butter 1 4 75 80 Soft cheese 0 2 80 85 Swiss che...

Page 11: ...notice liability the details of this technical documents serve for description Consents regarding the availability of certain features or regarding a certain purpose always require a special written...

Page 12: ...rtain features or regarding a certain purpose always require a special written agreement Page No 00044224 08 GB Viessmann K ltetechnik GmbH Schleizer Stra e 100 95030 Hof Saale Germany Phone 49 0 92 8...

Reviews: