The high limit safety cut-out must
not
be set higher
than 110 °C. If required, set it to a maximum of 110 °C.
Control unit installation and service instructions
Filling the heating system with water and venting
Record the volume filled, water hardness and pH value
on page 30.
Permissible boiler operating pressure: 6 bar (0.6 MPa).
!
Please note
Unsuitable water quality can result in damage to
the boiler body and the heating system.
Fill the heating system with water and operate it
in accordance with VDI Guideline 2035. The
total of alkaline earths must not exceed
0.02 mol/m
3
(total hardness 0.11 °dH).
Observe the "Water quality requirements" on
page 28.
Fully opening the rotary damper in the flue outlet and securing it
The rotary damper must be in the horizontal position.
Note
For correct handling of the rotary damper, see "Mini-
mising pulsation noise" on page 9.
Commissioning the system
Operating instructions for control unit, burner
and neutralising system, service instructions for
control unit, and burner manufacturer's docu-
mentation
0
1.
Check the heating system pressure.
Permissible boiler operating pressure: 6 bar
(0.6 MPa)
0
2.
Check that the installation room ventilation is
unobstructed.
0
3.
Check the gas supply pressure.
0
4.
Check that the cleaning aperture on the flue outlet
is closed.
0
5.
Open the gas line shut-off valves.
0
6.
Start the system in this order:
1. Mains isolator
2. Switch for the heating circuit pump
3. ON/OFF switch for the burner
Burner manufacturer's operating instruc-
tions
0
7.
Check the function of the neutralising system and
the hydraulic seal in the trap.
Neutralising system operating instructions
0
8.
Check all gaskets and plugs, and retighten if nec-
essary.
Note
We recommend checking all connections on the
heating water side for leaks approx. every 500
hours run. See page 11.
0
9.
Check the boiler door and cleaning cover a few
days after commissioning and retighten all screws.
10.
Tighten the screws at the connecting points with
the following torque:
Boiler door
20 Nm
Flange connections
110 Nm
Module connection
60 Nm
Flue gas collector
7 Nm
Danger
For safe operation, a minimum operating pres-
sure of 0.5 bar (50 kPa) is essential.
For this, a minimum pressure switch can be
used.
Commissioning, inspection, maintenance
Checking the high limit safety cut-out setting
5692910