32
Rated heating output
T
F/
T
R
= 50/30 °C
kW
787
978
1100
1400
T
F
/T
R
= 80/60 °C
kW
720
895
1006
1280
Rated heat input
kW
742
923
1038
1320
Product ID
CE-0085AU0315
Product parameters
(according to EnEV)
Standard seasonal efficiency [to
DIN]
At heating system temperature 40/30
°C
%
Up to 98 (H
s
) [gross cv]
At heating system temperature 75/60
°C
%
Up to 95 (H
s
) [gross cv]
Standby loss
q
B,70
%
0.25
0.25
0.25
0.25
Power consumption
■
At 100 % of rated heating output
W
1059
1175
—
—
■
At 30 % of rated heating output
W
353
140
—
—
Specification
Specification
5692910
Appendix