139
Checking the outside temperature sensor
A
1
2
1 2 3 4
B
B3
ATS B42/
B10
A
Outside temperature sensor
B
Junction box
100
10
-20 -10 0 10 20 30
Temperature in °C
6
8
20
40
60
80
200
Resistance in k
Ω
Sensor type: NTC 10 kΩ
1.
Pull plug "2K" from the control unit.
2.
Test the resistance of the outside
temperature sensor at the disconnec-
ted plug and compare it with the
curve.
3.
Where actual values deviate severely
from the curve values, disconnect the
wires at the sensor and repeat test on
the sensor itself.
4.
Depending on the result, replace the
lead or the outside temperature sen-
sor.
Troubleshooting
Repairs
(cont.)
5618 294 GB