43
Calling up coding level 1
■
On weather-compensated control units, codes are
displayed as plain text.
■
Codes that have not been assigned due to the heat-
ing system equipment level or the setting of other
codes are not displayed.
■
Heating systems with one heating circuit without
mixer and one or two heating circuits with mixer:
The heating circuit without mixer is designated
"Heating circuit 1"
and the heating circuits with
mixer as
"Heating circuit 2"
or
"Heating circuit 3"
.
If the heating circuits were given individual designa-
tions, the selected designation and
"HC1"
,
"HC2"
or
"HC3"
appear instead.
Weather-compensated control unit
Constant temperature control unit
The codes are divided into groups
■
"General"
■
"Boiler"
■
"DHW"
■
"Solar"
■
"Heating circuit 1/2/3"
■
"All codes std device"
In this group, all coding addresses from coding level 1
(except the coding addresses from the
"Solar"
group) are displayed in ascending order.
■
"Standard setting"
1
:
"General"
2
:
"Boiler"
3
:
"DHW"
4
:
"Solar"
5
:
"Heating circuit 1"
6
:
"All codes std device"
In this group, all coding addresses are displayed in
ascending order.
7
:
"Standard setting"
Call up code 1
Service menu:
1. Press
OK
and
å
simultaneously for approx. 4 s.
2.
"Coding level 1"
3. Select group of required coding address.
4. Select coding address.
5. Select value according to the following tables and
confirm with
OK
.
Service menu:
1. Press
OK
and
å
simultaneously for approx. 4 s.
2. Select
"
1
"
with
Ú
for coding level 1 and confirm with
OK
.
3.
"I"
flashes on the display for the coding addresses in
group 1.
4. Select the group of required coding address with
V
/
v
and confirm with
OK
.
5. Select coding address with
V
/
v
.
6. Set value according to the following tables with
V
/
v
and confirm with
OK
.
Resetting all codes to their delivered condition
Select
"Standard setting"
.
Note
This also resets the codes at coding level 2.
Select
"7"
with
Ú
and confirm with
OK
.
When
" "
flashes, confirm with
OK
.
Note
This also resets the codes at coding level 2.
"General"/Group 1
Select
"General"
for weather-compensated control
units (see page 43).
Select "1" for constant temperature control unit (see
page 43).
Code 1
Calling up coding level 1
5772 980 GB
Service