38
5
Heating circuit without mixer A1 (heating circuit 1)
6
Heating circuit with mixer M2 (heating circuit 2)
7
Temperature limiter to restrict the maximum tem-
perature of underfloor heating systems
8
Flow temperature sensor M2
9
Heating circuit pump M2
qP
Extension kit for one heating circuit with mixer M2
Heat exchanger for system separation
qW
Sub-mounting kit with mixer (accessory)
Function/system components
Code
Set
Group
Operation with LPG
82:1
"General"
System
only
with one heating circuit with mixer with extension kit for
mixer (without unregulated heating circuit)
■
With DHW cylinder or instantaneous water heater
00:4
"General"
■
Without DHW cylinder or instantaneous water heater
00:3
"General"
System
with
DHW circulation pump:
DHW circulation pump connected at internal extension H1 or H2
—
—
System version 4
One heating circuit without mixer, one heating circuit with mixer M2 (with extension kit), one heating cir-
cuit with mixer M3 (with extension kit) and low loss header (with/without DHW heating)
M
M
qU
qP
9
8
7
qW
qE
qR
qT
qZ
1
4
2
3
6
5
Fig. 34
ID: 4605149_1001_01
1
Vitodens 200-W
2
Outside temperature sensor
3
DHW cylinder
4
Cylinder temperature sensor
5
Heating circuit without mixer A1 (heating circuit 1)
6
Heating circuit pump A1
7
Heating circuit with mixer M2 (heating circuit 2)
8
Flow temperature sensor M2
9
Heating circuit pump M2
qP
Extension kit for one heating circuit with mixer M2
Heating circuit with mixer M3 (heating circuit 3)
qW
Temperature limiter to restrict the maximum tem-
perature of underfloor heating systems
qE
Flow temperature sensor M3
qR
Heating circuit pump M3
qT
Extension kit for one heating circuit with mixer M3
qZ
Low loss header
qU
Flow temperature sensor, low loss header
Function/system components
Code
Set
Group
Operation with LPG
82:1
"General"
System
only
with two heating circuits with mixer with extension kit for
mixer (without unregulated heating circuit)
■
With DHW cylinder or instantaneous water heater
00:8
"General"
■
Without DHW cylinder or instantaneous water heater
00:7
"General"
Commissioning, inspection, maintenance
Matching the control unit to the heating system
(cont.)