30
Check burner gasket
A
and burner gauze assembly
E
for possible damage and replace if required.
A
C
2x
2x
B
D
E
F
Fig. 24
1.
Remove electrodes
B
.
2.
Undo two retaining clips
C
on thermal insulation
ring
D
and then remove thermal insulation ring
D
.
3.
Undo two Torx screws and remove burner gauze
assembly
E
with gasket
F
.
4.
Insert new burner gauze assembly
E
with new
gasket
F
and secure.
Torque: 5.0 Nm.
5.
Fit thermal insulation ring
D
.
6.
Fit electrodes
B
.
Torque: 4.5 Nm.
Commissioning, inspection, maintenance
Checking the burner gasket and burner gauze assembly
5772 980 GB