30
The boiler is equipped with an electronic combustion
controller that adjusts the burner for optimum combus-
tion in accordance with the prevailing gas quality.
■
For operation with natural gas, no adjustment is
therefore required across the entire Wobbe index
range. The boiler can be operated within the Wobbe
index range 9.5 to 15.2 kWh/m
3
(34.2 to
54.7 MJ/m
3
).
1.
Check with your gas supply utility regarding the
gas type and Wobbe index.
2.
Record the gas type in the service report.
Removing the front panel
Danger
Contact with live components can lead to seri-
ous injury from electric current. Some compo-
nents on PCBs remain live even after the power
supply has been switched off.
■
Never touch
the wiring chambers (control unit
and power supply connections).
■
When working on the appliance, isolate the
system from the power supply, e.g. at a sepa-
rate MCB/fuse or a mains isolator. Check the
system is no longer live and safeguard against
reconnection.
■
Prior to working on the appliance, wait at
least 4 min until the voltage has completely
dropped out.
1.
2x
2.
3.
Fig. 18
Checking the static pressure and supply pressure
Danger
CO formation as a result of incorrect burner
adjustment can have serious health implications.
Always carry out a CO test before and after
work on gas appliances.
Commissioning, inspection, maintenance
Checking the gas type
6174240