21
Filling the trap with water
Fig. 10
Pour at least 0.3 l of water into the flue gas connection.
!
Please note
During commissioning, flue gas may escape
from the condensate drain.
Always fill the trap with water before commis-
sioning.
Note
If there is a risk of frost, only fill the trap just before
commissioning.
Flue gas connection
Note
The labels "System certificate" and "Skoberne GmbH
or Groppalli flue system" enclosed with the technical
documentation may only be used in conjunction with
the Viessmann flue system made by Skoberne or
Groppalli.
Connecting the balanced flue pipe
Flue system installation instructions
Gas connection
A
Fig. 11
1.
If the gas connection has not been fitted previ-
ously, seal gas shut-off valve
A
to the gas con-
nection.
When carrying out any work on gas connection fit-
tings, hold with a suitable tool. Never transfer any
forces to the internal components.
Installation sequence
Condensate connection
(cont.)
6174240
Installation