123
Type AWT-AC
221.B10
221.B13
221.B16
Heating output data
to EN 14511
(A7/W35, 5 K spread)
Rated heating output
kW
10.16
12.07
15.5
Fan speed
rpm
600
690
690
Air flow rate
m
3
/h
3456
4217
4217
Power consumption
kW
2.00
2.57
3.76
Coefficient of performance
ε
(COP) in heating mode
5.08
4.69
4.11
Output control
kW
5.20 to 15.00
6.20 to 16.50
—
Heating output data
to EN 14511
(A
–
7/W35)
Rated heating output
kW
9.50
10.70
13.3
Power consumption
kW
3.06
3.69
5.12
Coefficient of performance
ε
(COP) in heating mode
3.10
2.90
2.59
Cooling capacity data
to EN 14511
(A35/W7, 5 K spread)
Rated cooling capacity
kW
9.14
10.75
11.85
Fan speed
rpm
600
690
690
Power consumption
kW
3.37
4.15
5.58
Energy efficiency ratio EER
2.71
2.59
2.17
Output control
kW
1.96 to 9.85
2.14 to 11.45
—
Cooling capacity data
to EN 14511
(A35/W18, 5 K spread)
Rated cooling capacity
kW
8.83
12.83
14.22
Fan speed
rpm
600
690
690
Power consumption
kW
1.98
3.45
4.23
Energy efficiency ratio EER
4.46
3.72
3.43
Air intake temperature
Cooling mode
■
Min.
°C
15
15
15
■
Max.
°C
45
45
45
Heating mode
■
Min.
°C
–
20
–
20
–
20
■
Max.
°C
35
35
35
Heating water
(secondary cir-
cuit)
Content
l
17.7
17.7
17.7
Minimum flow rate (must be
maintained)
l/h
1600
1600
1600
Minimum volume in the heating
system (cannot be fitted with
shut-off devices)
l
50
50
50
Max. external pressure drop
(RFH) at minimum flow rate
mbar
450
450
450
kPa
45
45
45
Max. flow temperature
°C
55
55
55
Specification
Specification
(cont.)
5700 562 GB
Appendix