36
Installation and Assembly
IM-HC 599871 0321 RABS
Figure 20: Control unit sockets, cable clip, and lithium back-up battery
Locating the Control Unit
There are three mounting holes located in three corners of the rear
housing. Three bushings, three drywall anchors, and three screws are
included with each control unit.
Install Location and Access Clearance
Both the long ribbon cable and the supply sensor are about
31.5 inches long. Verify both ends of each cable can reach
their contact points before deciding where to install the
control unit. Maintain at least two inches of clearance
around the housing faceplate to ensure access to the
control unit in the future.
X
Mount the Control Unit above the manifold.
X
Pull out the inserted lithium battery’s transport lock.
X
Reattach the housing faceplate. First, align the two holes on the
housing faceplate with the two flexible hinges on the left side of the
rear housing. Then click the latch on the right side into place.
AKT
OR
VL-TEM
P
TAUP
.
RS-232
RESET
AK
TO
R
VL-TEM
P
TA
UP
.
RS-232
RESET