3 Handling
3.1
Assembly information
3.1.1
Permitted exchange of sealing elements
Important instruction
With their material-specific qualities, sealing elements in
press connectors are adapted for use with the corre‐
sponding media and/or the areas of use of the piping sys‐
tems and are generally only certified for them.
The exchange of a sealing element is generally permitted.
The sealing element must be exchanged for a designated
spare part for the intended application
„Sealing elements“ on page 10. The use of other sealing ele‐
ments is not permitted.
3.1.2
Mounting instructions
Do not remove the model from the packaging until immedi‐
ately before use.
System components may, in some cases, become damaged through
transportation and storage.
n
Check all parts.
n
Replace damaged components.
n
Do not repair damaged components.
n
Contaminated components may not be installed.
Observe the following when mounting:
n
use suitable tools
n
flow direction indicator
n
When tightening the connection screw fitting, counter by holding the
key surface of the valve.
n
A piece of straight pipe of at least 3xd should be installed upstream
from the fitting.
Choose the place of installation so that the fitting is easily
accessible, simple to operate and the insulating shell can be
well mounted.
Checking system components
During assembly
Handling
Easytop circulation regulation valve, static regulation valve with SC-Contur