66550033-EN - V4.0 - 15/02/19
- 14 -
ESVK/6388 Series “2 wire Bus” videokit
ESVK/6388 Series - Installation handbook
BUILT-IN RELAYS – BACK EMF PROTECTION
The Art. 4800M includes selectable back EMF protection on the relays. The jumpers marked
MOV
(One jumper for each relay) are used
to select the protection type. When using a fail secure lock with connections
C
&
NO
the jumper should be in the
NO
position. When
using a fail open lock with connections
C
&
NC
the jumper should be in the
NC
position and when using the codelock to trigger a gate
controller or another third party controller the jumper should be removed completely (this disables the protection on the relay).
PROGRAMMING
• Enter the
ENGINEER’S CODE
: first time type six times
1
(
111111
factory preset) and press
ENTER
(The red LED will illuminate);
• Confirm
ENGINEER’S CODE
(typing again the same) or
type the new code (4 to 8 digits) then press
ENTER
(Melo-
dy). Pressing twice the
ENTER
button without changing the
ENGINEER’S CODE
, will exit from the programming;
• Enter the code (4 to 8 digits) to enable
RELAY 1
or re-enter the
existing code then press
ENTER
(Melody);
• Enter the
RELAY 1
operation time (2 digits 01 to 99
I.E.
05=5
seconds, 00= remain open time) or re-enter the existing time
then press
ENTER
(Melody);
• Enter the code (4 to 8 digits) to enable
RELAY 2
or re-enter the
existing code then press
ENTER
(Melody);
• Enter the
RELAY 2
operation time (2 digits 01 to 99
I.E.
05=5
seconds, 00= remain open time) or re-enter the existing time
then press
ENTER
(Melody);
• Enter the code (4 to 8 digits) to enable
RELAY 3
or re-enter the
existing code then press
ENTER
(Melody);
• Enter the
RELAY 3
operation time (2 digits 01 to 99
I.E.
05=5
seconds, 00= remain open time) or re-enter the existing time
then press
ENTER
(Melody);
• The system is ready to use (the red LED will be off).
PROGRAMMING NOTES
• After pressing enter following a command, press
ENTER
a fur-
ther twice to exit the programming menu.
RETURN SYSTEM TO PRESET ENGINEER’S FACTORY CODE
• Turn off power to code lock;
• Keep
ENTER
button pressed while turning the power back on;
• Release
ENTER
button;
• The engineer’s code is now set to
111111
(six times one).
OPERATION
• Type in the programmed code and press
ENTER
;
• If the code is correct, the green LED will illuminate for approx. 2 seconds and the relay relevant to the code will operate for the
programmed time;
• If a wrong code is entered, a continuous melody will sound for 4 or more seconds, according to the number of mistakes;
• To switch off any relay while operating, type in the relevant code then press the
CLEAR
button;
OPERATION NOTES
• To operate relays together, set the same code for each relay;
• If a wrong code is entered, the system will lock out for 5 seconds which will increase each time a wrong code is entered. The system will
operate only when the correct code is entered.
ENTER THE
"ENGINEER’S CODE"
CONFIRM
OR CHANGE
"ENGINEER’S CODE"
ENTER
"ACCESS 1 CODE"
ENTER
"ACCESS 2 CODE"
ENTER
"ACCESS 3 CODE"
ENTER
"ACCESS 1 TIME"
ENTER
"ACCESS 2 TIME"
ENTER
"ACCESS 3 TIME"
SYSTEM
READY TO USE
First time six times
1 “111111” factory
preset
Type again six times
“1” or the new en-
gineer’s code 4 to 8
digits
Code to enable relay 1
4 to 8 digits
Code to enable relay 2
4 to 8 digits
Code to enable relay 3
4 to 8 digits
Two digits (01 to 99)
i.E. 05=5 Seconds
00= remain open
Two digits (01 to 99)
i.E. 05=5 Seconds
Two digits (01 to 99)
i.E. 05=5 Seconds
Red led will be off
Press Enter
(Red LED will
be ON)
Press Enter
(melody)
Press Enter
(melody)
Press Enter
(melody)
Press Enter
(melody)
Press Enter
(melody)
Press Enter
(melody)
Press Enter
(melody)