Parallel operation (see appendix C)
Step 1: Setting ds2 and ds1 for parallel operation
The current settings (AC current limitation and charging current) are multiplied by the number of devices. However, the AC
current limitation setting when using a remote panel will always correspond to the value indicated on the panel and should
not
be multiplied by the number of devices.
Example: 15kVA parallel system
- If an AC-in-1 current limitation of 20A is set on the master and the system consists of three devices, then the effective system
current limitation for AC-in-1 is equal to 3 x 20 = 60A (setting for generator power 60 x 230 = 13.8kVA).
- If a 30A panel is connected to the master, the system current limitation for AC-in-2 is adjustable to a maximum of 30A,
regardless of the number of devices.
- If the charging current on the master is set to 100% (120A for a Quattro 24/5000/120) and the system consists of three
devices, then the effective system charging current is equal to 3 x 120 = 360A.
The settings according to this example (15kVA parallel system) are as follows:
Master
Slave 1
Slave 2
DS-8 AC-in-1 (3 x 20 = 60A)
on
DS-7 AC-in-1 (3 x 20 = 60A)
off
DS-6 AC-in-1 (3 x 20 = 60A)
off
DS-5 AC-in-2 na (30A panel)
DS-4 Charging current 3x120A
on
DS-3 Charging current 3x120A
on
DS-2 Master
off
DS-1 Master
on
DS-8 na
DS-7 na
DS-6 na
DS-5 na
DS-4 na
DS-3 na
DS-2 Slave 1
off
DS-1 Slave 1
off
DS-8 na
DS-7 na
DS-6 na
DS-5 na
DS-4 na
DS-3 na
DS-2 Slave 2
off
DS-1 Slave 2 on
To store the settings after the required values have been set: press the 'Up' button of the
master
for 2 seconds (
upper
button
to the right of the DIP switches, see appendix A, position K).
The overload and low-battery LEDs will flash to indicate
acceptance of the settings.
We recommend making a note of the settings, and filing this information in a safe place.
You can now re-use the DIP switches to apply the remaining settings (step 2).
Master
Slave 1
Slave 2 (optional)
DS-8 AC-in-1 Set
DS-7 AC-in-1 Set
DS-6 AC-in-1 Set
DS-5 AC-in-2 Set
DS-4 Ch. current Set
DS-3 Ch. current Set
DS-2 Master
off
DS-1 Master
on
DS-8 na
DS-7 na
DS-6 na
DS-5 na
DS-4 na
DS-3 na
DS-2 Slave 1
off
DS-1 Slave 1
off
DS-8 na
DS-7 na
DS-6 na
DS-5 na
DS-4 na
DS-3 na
DS-2 Slave 2
off
DS-1 Slave 2 on
Summary of Contents for Quattro 12/5000/200
Page 2: ......
Page 4: ......
Page 54: ......
Page 80: ......
Page 104: ......
Page 130: ......
Page 131: ...EN NL FR DE ES Appendix APPENDIX A Overview connections B H M K G F E J I L C D A C O P N ...
Page 134: ...APPENDIX B Block diagram ...
Page 135: ...EN NL FR DE ES Appendix APPENDIX C Parallel connection ...
Page 136: ...APPENDIX D Three phase connection ...
Page 139: ...EN NL FR DE ES Appendix APPENDIX G Dimensions ...
Page 140: ......
Page 141: ......