13
EN
NL
F
R
DE
ES
A
p
p
e
n
d
ix
5.2 Explanation of settings
Settings that are not self-explanatory are described briefly below. For further information,
please refer to the help files in the software configuration programs (see Section 5.3).
Inverter frequency
Output frequency if no AC is present at the input.
Adjustability: 50Hz; 60Hz
Input frequency range
Input frequency range accepted by the MultiPlus. The MultiPlus synchronises within this
range with the AC input frequency. The output frequency is then equal to the input
frequency.
Adjustability: 45 – 65Hz; 45 – 55Hz; 55 – 65Hz
Input voltage range
Voltage range accepted by the MultiPlus. The MultiPlus synchronises within this range
with the AC input voltage. The output voltage is then equal to the input voltage.
Adjustability:
Lower limit: 180 - 230V
Upper limit: 230 - 270V
Inverter voltage
Output voltage of the MultiPlus in battery operation.
Adjustability: 210 – 245V
Stand-alone / parallel operation / 2-3 phase setting
Using several devices, it is possible to:
increase total inverter power (several devices in parallel)
create a split-phase system
create a 3-phase system.
The standard product settings are for standalone operation. For parallel, three phase or split
phase operation see section 4.4.5 and 4.4.6.
Search mode
If search mode is ‘on’, the power consumption in no-load operation is decreased by approx.
70%. In this mode the MultiPlus, when operating in inverter mode, is switched off in case of no
load or very low load, and switches on every two seconds for a short period. If the output
current exceeds a set level, the inverter will continue to operate. If not, the inverter will shut
down again.
Search Mode can be set with a DIP switch.
Search Mode ‘shut down’ and ‘remain on’ load levels can be set with VEConfigure.
The standard settings are:
Shut down: 30 Watt (linear load)
Turn on: 60 Watt (linear load)
AES (Automatic Economy Switch)
Instead of the search mode, the AES mode can also be chosen (with help of VEConfigure
only).
Summary of Contents for MultiPlus 12/800/35
Page 22: ......
Page 44: ......
Page 66: ......
Page 88: ......
Page 110: ......
Page 111: ...EN NL FR DE ES Appendix www victronenergy com Appendix A overview connections ...
Page 113: ...EN NL FR DE ES Appendix www victronenergy com Appendix B installation information ...
Page 117: ...EN NL FR DE ES Appendix www victronenergy com APPENDIX F dimensions ...
Page 118: ......
Page 119: ...www victronenergy com ...