                                             IOM – VL71 FLOODLIGHT

 

  

VL71 IOM

 IECEx 

ATEX    

Issue 02  

May 08   

 

 

7

0.0 Tables 0/1/2 

Table 0                          Lamp Ranges and Temperature Ratings                                      Refer to Section : 1.0

Lamp 

Wattage 

Rated Supply 

T Class 

T amb 

ºC

Min

Ambient 

ºC

Rated 
Cable

ºC

Cable Temperature Rise 

Above Ambient 

T/HAL 500 

220-254V 

T3 

55 

70 

15 

 

 

 

 

 

 

 

SON/T 400 

T3 

50 

70 

20 

 250 

T4 55 

70 

15 

 150 

T4 60 

70 

10 

 

 

 

 

 

 

 

 

 

 

 

 

MBI/T 400 

T3 

50 

70 

20 

 250 

T4 55 

70 

15 

 150 

220-254V …50/60Hz 

T4 60 

70 

10 

 

 

 

 

 

 

 

400 T3 

55 

80 

25 

250 T4 

55 

70 

15 

SON/T 

150 T4 

 

55 

70 

15 

400 T3 

55 

80 

25 

250 T4 

55 

70 

15 

MBI/T 

150

110-120V 50/60Hz 

T4 55 

-50ºC 

70 15 

Table 1                             Starting and Running Currents                                                   Refer to section : 4.0 

LAMP 

Lamp A 

Start A 

Run A 

Capacitance 

μ

Circuit Power  (W) 

150W SON/T 

1.8 

1.45 

0.8 

20 

175 

250W SON/T 

3.0 

2.35 

1.3 

30 

285 

400W SON/T 

4.6 

4.0 

2.2 

40 

445 

150W MBI 

1.8 

1.6 

0.8 

20 

175 

250W MBI 

3.0 

2.7 

1.35 

30 

285 

400W MBI 

4.2 

4.0 

2.2 

40 

445 

Notes:

    

Minimum power factor correction:  0.85. 

 

 

 

The start and running currents are corrected. 

Table 2                             Fuse Ratings                                                                               Refer to section :  4.0 

Number of Lamps 

Lamp 

1 2 3 4 5 6 

150W 4A  6A  10A 10A 16A 16A 
250W 10A 16A 16A 20A 20A 20A 
400W 16A 20A 20A 25A 25A 32A 

Summary of Contents for VL71

Page 1: ...ION OPERATION AND MAINTENANCE INSTRUCTIONS Victor VL71 FLOODLIGHT IECEx ATEX Important Please read these instructions carefully before installing or maintaining this equipment Good electrical practices should be followed at all times and this data should be used As a guide only ...

Page 2: ...er 1 0 Introduction VL71 nR FLOODLIGHT The VL71 Floodlight is designed for all round lighting applications It is suitable for use with tubular discharge lamps and single ended tungsten halogen lamps A gear box is used with the low voltage range of 400w HID versions The floodlight is restricted in its mounting position The beam of the floodlight may be aimed at any angle but the control gear must a...

Page 3: ... where the dust could lie on the glass The temperature on the glass is the hottest point on the luminaire and any obstruction of the radiation from the luminaire would cause the surface temperature to increase 3 2 Tools A cross head screwdriver blade to open hinged cover 3mm and 5mm flat blade screwdriver Suitable spanners for installing cable glands Pliers knife wire strippers cutters 3 3 Electri...

Page 4: ...mply with the certification for installation and use within the EU cable glands and sealing plugs must have ATEX component approval For installation outside the EU suitable cable glands in accordance with IECEx EN 60079 0 will meet the technical requirements The cable and gland assembly when installed must maintain the IP66 67 rating of the floodlight The cable gland must withstand an impact value...

Page 5: ... should be opened up dried out and any likely ingress points eliminated by re gasketting re greasing or other replacement 3 Check the cable gland for tightness and tighten if necessary 4 Check any external earthing 5 Examine the glass for any signs of damage Clean glass 6 When relamping check that the cover gasket has not softened or become excessively deformed if in doubt replace see section 4 0 ...

Page 6: ...er judgement of what is required Use MCB s suitable for inrush currents to reduce ratings The normal capacitor current will probably be the determining factor 0 076A per μF at 240V 50Hz adjust for other volts by multiplication x 6 5 for 60Hz For HBC fuses use 1 5 x normal capacitor current For GLS inrush use 6 x rated current All calculations must satisfy wiring regulations Note Starting and runni...

Page 7: ... SON T 150 T4 55 70 15 400 T3 55 80 25 250 T4 55 70 15 MBI T 150 110 120V 50 60Hz T4 55 50ºC 70 15 Table 1 Starting and Running Currents Refer to section 4 0 LAMP Lamp A Start A Run A Capacitance μF Circuit Power W 150W SON T 1 8 1 45 0 8 20 175 250W SON T 3 0 2 35 1 3 30 285 400W SON T 4 6 4 0 2 2 40 445 150W MBI 1 8 1 6 0 8 20 175 250W MBI 3 0 2 7 1 35 30 285 400W MBI 4 2 4 0 2 2 40 445 Notes Mi...

Page 8: ...44 Fax 44 0 141 810 9642 Email info victor lighting com Web www victor lighting com For Technical support please contact technical victor lighting com Registered Office Mitre House 160 Aldersgate Street London EC1A 4DD Registered No 669157 Note Victor Lighting reserve the right to amend characteristics of our products and all data is for guidance only ...

Reviews: