Installation Guide
39
Power Supply and Grounding
The power supply terminal block is shown in the figure below. The terminal block is
included with the panel.
Figure 35 - Power supply terminal block
Note
: ensure that the power supply has enough power capacity for the operation
of the equipment.
The unit must always be grounded to earth. Grounding helps limit the effects of noise
due to electromagnetic interference on the control system.
Earth connection will have to be done using either either the screw or the faston
terminal located near the power supply terminal block. A yellow label help identify
the ground connection. Also connect to ground the terminal 3 on the power supply
terminal block.
The power supply circuit may be floating or grounded. In the latter case connect to
ground the power source common as shown in figure 42 with a dashed line.
When using the floating power scheme, note that the panels internally connect the
power commond to ground with a 1 M
Ω
resistor in parallel with a 4,7 nF capacitor.
The power supply must have double or reinforced insulation
The suggested wiring for the power supply is shown in figure 36.
Summary of Contents for UniOP BKDC-46
Page 4: ...UniOP ii...
Page 19: ...Installation Guide 15 BKDR 16 Figure 4 Dimensions...
Page 20: ...UniOP 16 BKDC 46 275mm 10 82 5mm 0 16 8 66 220mm 262mm 10 31 206mm 8 11 Figure 5 Dimensions...
Page 24: ...UniOP 20 eTOP04C Figure 10 Dimensions...
Page 34: ...UniOP 30 Connections MD02R 04 Figure 20 Connectors CP01R 04 CP02R 04 Figure 21 Connectors...
Page 40: ...UniOP 36 BKDC 46 POWER PLC PORT PC PRINTER AUX PORT FUSE Figure 32 Connectors...