23 |
028-0325-02_LIT-VZ7656F_W-E01_EN
October 2019
Channel
Channel selection
Default value = 10
Range is:
10 to 26
This parameter (Channel) is used to link specific
controllers to specific Viconics wireless gateway(s) (VWG
/ Jace-Driver) or to the main VZ76xx RTU controller. For
any system, be sure you set the
SAME
channel value
both at the network coordinator and on all the VZ72xx
controller(s).
Viconics recommends using only the following channels:
15, 25 & 26.
The default value of 10 is
NOT
a valid channel. The valid
range of available channels range from 11 to 26.
Lockout
Keypad lockout levels
Default value =
0 No lock
0 = No lock
1 = Low level
2 = High level
USER KEY FUNCTIONS
LEVEL
Global
Unocc.
Override
System mode
setting
Schedules
setting
Clock setting
0
1
2
pwr del
Power-up delay
(
Default value =
10 seconds
On initial power up of the Terminal Equipment Controller
each time 24 VAC power supply is removed & re-applied)
here is a delay before any operation is authorized (fan,
cooling or heating). This can be used to sequence start
up multiple units / Terminal Equipment Controller in one
location.
10 to 120 seconds