background image

15 | 

028-0325-02_LIT-VZ7656F_W-E01_EN 

www.viconics.com

 

October 2019

 

Override

 

Resume

 

 

Override 

schd Y/N

 

Appears only in 

unoccupied mode 

 

System mode

 

setting

 

 

Sys mode 

set Y/N

 

 

Schedules

 

setting

 

 

Schedule 

set Y/N

 

 

Clock setting

 

 

Clock 

set Y/N

 

 

If the user pauses at any given time during configuring, 

Auto Help 

text is displayed to 

help and guide the user through the usage and configuring of the controller. 

 

 

Ex.: 

Press yes key to change cooling temperature setpoint 

Use the up or down arrow to adjust cooling setpoint 

 

Each of the sections in the menu is accessed and configured using 5 keys on the 

controller cover. The priority for the alarms is as follows: 

 

Local keypad interface

 

 

 

 

The YES key is used to confirm a selection, to move onto the next menu item 

and to manually scroll through the displayed information. 

 

 

The NO key is used when you do not desire a parameter change, and to 

advance to the next menu item. Can also be used to toggle between heating 

and cooling setpoints. 

 

 

 

The MENU key is used to access the Main User Menu or exit the menu. 

 

 

The down arrow key is used to decrease temperature setpoint and to adjust 

the desired values when configuring the Terminal Equipment Controller. 

 

 

The up arrow key is used to increase temperature setpoint and to adjust the 

desired values when configuring the Terminal Equipment Controller. 

 

When left unattended for 45 seconds, the display will resume automatic status 

display scrolling. 

 

To turn on the back light, press any key on the front panel. The back lit display will 

turn off automatically after 45 seconds. 

 

Sequence of user menu: 

 

 

 

Appears only in 

override mode 

Cancel 

ovrd Y/N

 

Summary of Contents for VZ7656F1000W

Page 1: ...14 Installer Configuration Parameter Menu 19 Specifications 30 Drawing Dimensions 31 NOTICE IMPORTANT NOTICE RELATED TO PRODUCT PART NUMBERS For the latest model and part numbers please refer to VT80...

Page 2: ...t follow this symbol to avoid possible injury or death DANGER DANGER indicates a hazardous situation which if not avoided will result in death or serious injury WARNING WARNING indicates a hazardous s...

Page 3: ...Lead and Bisphenol A BPA which are known to the State of California to cause cancer and birth defects or other reproductive harm For more information go to www P65Warnings ca gov Failure to follow the...

Page 4: ...Refer to the Room Controller User Interface Guide for information on how to configure the Room Controller Failure to follow these instructions can result in equipment damage Location NOTICE LOCATION...

Page 5: ...Should not be affected by direct sun radiation 5 Nothing should restrict vertical air circulation to the Terminal Equipment Controller Installation 1 Swing open the Terminal Equipment Controller PCB...

Page 6: ...h virtually eliminates temperature offset associated with traditional differential based on off thermostats Fig 2 On Off mechanical control vs PI electronic control Features overview 7 day schedule mo...

Page 7: ...ntact RemOVR temporary occupancy contact Disables all override menu function of the Terminal Equipment Controller The override function is now controlled by a manual remote momentarily closed contact...

Page 8: ...operating typical single or multistage RTU s and their associated local zones For example a typical job layout system may feature 3 RTU controllers and a total of 31 zones This would bring to total n...

Page 9: ...Used Not Used 8 Auxiliary Output AU Auxiliary output used to disable economizer damper minimum position or control lighting during unoccupied periods 9 By pass damper BPD Local analog 0 10 VDC by pas...

Page 10: ...dded for additional functionality of the occupancy output Note 2 Analog outputs and inputs use a half bridge rectifier Reference of the control signal is the common of the power supply of the Terminal...

Page 11: ...94 50 122 3 6202 29 20 161 1499 9 16 51 3692 11 52 18 8277 31 88 7 7360 51 124 3 4857 28 18 151 6239 8 18 48 7042 12 54 17 9636 32 90 7 4182 52 126 3 3568 27 17 142 7211 7 19 46 1933 13 55 17 1440 33...

Page 12: ...TRUCTIONS Status display The Terminal Equipment Controller features a two line eight character display There is a low level backlight that is always active and can only be seen at night When left unat...

Page 13: ...h as mode lockouts and economizer function are automatically disabled Alarms If alarms are detected they will automatically be displayed at the end of the status display scroll During an alarm message...

Page 14: ...failure which has lasted longer than 6 hours Filter Indicates that the filters are dirty as per one of the configurable digital input DI1 or DI2 Com Lost The communication between devices has been lo...

Page 15: ...lection to move onto the next menu item and to manually scroll through the displayed information The NO key is used when you do not desire a parameter change and to advance to the next menu item Can a...

Page 16: ...ume regular scheduling This menu does not appear in regular operation It will appear only when the controller is in override mode Answering Yes to this question will cause all the zones attached to th...

Page 17: ...es next No down Yes Will copy previous day schedule No Daily schedules will be accessed Yes key to copy previous day No key to set new time value for each day Occupied 00 00 AM Use To set value Occupi...

Page 18: ...es down Wednesda set Y N No next Yes down Selects the day to be scheduled or modified Yes key to access day scheduling No key to jump to next day Occupied Day Y N No next Yes down Occupied Day Y N No...

Page 19: ...s This section of the menu permits the user to set the time andday Time setting Day setting Time format setting Time set Y N No next Yes down Day set Y N No next Yes down 12 24hrs set Y N No exit Yes...

Page 20: ...ntroller Controller network address Default Value 4 RTC MAC address must be unique for the entire network 1 to 255 Increments 1 or 10 For BACnet models valid range to use is from 1 to 127 PAN ID Perso...

Page 21: ...twork coordinator Range of PAN ID on all controllers to use 251 to 500 This range is reserved for stand alone system operation Examples System 1 RTU VZ76 Coordinator Channel 25 ID 200 Zone VZ72 Router...

Page 22: ...T7xxx wireless controllers act as routers Range of PAN ID on all controllers to use 1 to 250 Reservedfor networked system operation Examples Coordinator Channel 25 ID 200 System 1 RTU VZ76 Router Chan...

Page 23: ...5 25 26 The default value of 10 is NOT a valid channel The valid range of available channels range from 11 to 26 Lockout Keypad lockout levels Default value 0 No lock 0 No lock 1 Low level 2 High leve...

Page 24: ...ll dictate heating or cooling operation of the RTU controller 2 AV_H5 The average of the 5 highest PI Heating or PI Cooling demands from the selected voting zones will dictate heating or cooling opera...

Page 25: ...the maximum number of cycles that the equipment will be turned on and off in the span of an hour Note that a higher C P H will represent a higher accuracy of control at the expense of wearing down mec...

Page 26: ...now possible to toggle between unoccupied occupied RTU operation modesfor the amount of time set by the parameter TOccTime Temporary occupancy time When override is enabled an override status message...

Page 27: ...based on outdoor air temperature Function will only be enabled if OS outside air temperature sensor is connected From 15 F up to 120 F 26 C up to 49 C C lock Outside air temperature mechanical coolin...

Page 28: ...the system will restart and send the occupied status to the attached zones On progressive recovery active The configured occupied schedule time is the time at which the desired occupied temperature s...

Page 29: ...0 to 5 VDC 0 0 to 1 5 in WC 1 0 to 2 in WC 2 0 to 3 in WC 3 0 to 4 in WC 4 0 to 5 in WC Pressure Static Pressure setpoint Default 0 8 WC Bypass damper will maintain this supply static pressure set po...

Page 30: ...0 2 F 0 5 C 0 9 F 21 C 70 F typical calibrated Relay outputs 30 VAC 1 Amp Maximum 3 Amp In rush 12 0 to 37 5 C 54 to 100 F 4 5 C to 32 C 40 F to 90 F 40 C to 50 C 40 F to 122 F Dry contact across ter...

Page 31: ..._W E01_EN www viconics com October 2019 DRAWING DIMENSIONS Viconics Technologies Inc 7262 Marconi Street I Montreal I Quebec I Canada I H2R 2Z5 Tel 514 313 8885 I Toll free 1 800 563 5660 sales viconi...