background image

1 | 028-0377-03  

 

 

 

 

      November 2015 

 

 

 

 

INSTALLATION................................................................................................ 2 

Location ......................................................................................................... 2 

Installation ..................................................................................................... 2 

TERMINAL, IDENTIFICATION AND FUNCTION ............................................... 4 

Screw terminal arrangement and wiring ....................................................... 5 

TYPICAL APPLICATIONS.................................................................................. 5 

Main outputs wiring ...................................................................................... 6 

CONFIGURING AND STATUS DISPLAY INSTRUCTIONS ................................... 9 

Status display ................................................................................................. 9 

USER INTERFACE .......................................................................................... 11 

User configuring instructions menu ............................................................ 11 

Local keypad interface ................................................................................. 11 

 

 

 

 

 

 

  

  

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

 

ONTENTS

 

 

 

VT7600F Series 

Installation Guide 

November 2015

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for VT7600F Series

Page 1: ... FUNCTION 4 Screw terminal arrangement and wiring 5 TYPICAL APPLICATIONS 5 Main outputs wiring 6 CONFIGURING AND STATUS DISPLAY INSTRUCTIONS 9 Status display 9 USER INTERFACE 11 User configuring instructions menu 11 Local keypad interface 11 CONTENTS VT7600F Series Installation Guide November 2015 ...

Page 2: ...tion to Room Controller Installation 1 Swing open Room Controller PCB to left by pressing PCB locking tabs fig 2 2 Pull cables 6 out from wall Ensure wall surface is flat and clean 3 Insert cable in central hole of base 4 Align base and mark location of two mounting holes on wall ensuring base is in proper orientation Arrow on base should be facing up 5 Install anchors in wall 6 Insert screws in m...

Page 3: ...T7000 series Room Controllers are designed for use as operating controls only and are not safety devices These instruments have undergone rigorous tests and verification prior to shipping to ensure proper and reliable operation in the field Whenever a control failure could lead to personal injury and or loss of property it becomes the responsibility of the user or installer or electrical system de...

Page 4: ...AO analog heat AO Analog 0 10 VDC heating output 10 Auxiliary output AUX Auxiliary output used to disable economizer minimum position or control lighting during unoccupied periods 11 DI 1 DI 1 Configurable extra digital input See parameter section for more information 12 DI 2 DI 2 Configurable extra digital input See parameter section for more information 13 RS RS Remote temperature sensor input 1...

Page 5: ...5 028 0377 03 November 2015 Screw terminal arrangement and wiring VT76XXF Controller Terminals Y2 Y1 AO Aux RS SCom OS MS TYPICAL APPLICATIONS G RC C DI1 DI2 ...

Page 6: ...fier Reference of the control signal is the common of the power supply of the Room Controller Terminal C Note 4 Electromechanical contacts are to be used with the digital inputs Electronic triacs cannot be used as mean of switching for the input The switched leg to the input for the input to activate is terminal C common Note 5 The transformer of the unit provides power to the t Room Controller an...

Page 7: ...9 48 20 7004 29 84 8 4190 49 120 3 7607 30 22 171 3474 10 14 54 1988 10 50 19 7390 30 86 8 0694 50 122 3 6202 29 20 161 1499 9 16 51 3692 11 52 18 8277 31 88 7 7360 51 124 3 4857 28 18 151 6239 8 18 48 7042 12 54 17 9636 32 90 7 4182 52 126 3 3568 27 17 142 7211 7 19 46 1933 13 55 17 1440 33 91 7 1150 53 127 3 2333 26 15 134 3971 6 21 43 8268 14 57 16 3665 34 93 6 8259 54 129 3 1150 25 13 126 6109...

Page 8: ... installed in the fresh air plenum Supply air temperature averaging sensor for economizer models with the sensor in the mixing plenum S2020E1000 outdoor air temperature sensor This sensor can be used for Outside air temperature sensing with the sensor installed directly exposed to the elements Sensor uses a water resistant NEMA 4 ABS enclosure for outdoor applications WIRING S2000D1000 S2060A1000 ...

Page 9: ...ODE SCHEDULE STATUS OUTDOOR TEMPERATURE ALARMS Monday 12 00 AM Sys mode auto Occupied Outdoor x x C or F Service Sys mode off Occupied hold Frost ON Sys mode heat Unoccup SetClock Sys mode cool Filter Fan lock DAS Alrm Outdoor air temperature Outdoor air temperature display is only enabled when outdoor air temperature sensor is connected A maximum range status display of 50 C 122 F indicates a sho...

Page 10: ...tes that there is a service alarm as per one of the configurable digital input DI1 or DI2 Filter Indicates that the filters are dirty as per one of the configurable digital input DI1 or DI2 Fan lock Indicates that the heating and cooling action are locked out due to a defective fan operation DAS Alarm Indicates that the discharge air temperature is either too low or too high When any of the fan is...

Page 11: ...usage and configuring of the controller Local keypad interface The YES key is used to confirm a selection to move onto the next menu item and to manually scroll through the displayed information The NO key is used when you do not desire a parameter change and to advance to the next menu item Can also be used to toggle between heating and cooling setpoints The MENU key is used to access the Main Us...

Page 12: ...12 028 0377 03 November 2015 Viconics Technologies Inc Tel Fax Toll free www viconics com ...

Reviews: