Servicing
51
parameter
function
adjustment
range/adjustment
Pr 13
Heat pump stroke
00
00 = pump controlled by the indoor unit
04 = pump runs continuously
Pr 14
Ignition performance
Dependence
(determines)
Pr 01
00 ( = 0%) … 100 ( = 100 %)
Pr 15
OTC selection
00
00 = OFF
01 = ( = 0,1 ) … 60 ( =6,0) K value
Pr 16
Heating power MIN
Dependence
(determines)
Pr 01
00 ( =0%) … 100 ( =100%)
Pr 17
HW heating
- for combined version only
00
00 = burner STOP fixed at T
TV
= 65 °C
01 = burner STOP at T
boilermax
+ 5 °C
Pr 17
Antilegionella
- for stationary boiler only
00
00 = OFF
01 = every two days
02 = every three days
Pr 18
Reverse
00
00 = reverse not measured
01 = reverse measured
02 = TBD
03 = ( = 3 °C) … 30 ( = 30 °C)
∆
T
maintained between outlet and reverse
Pr 19
User Interface
Dependence
(determines)
Pr 01
00 = UI 585561 (bar/°C)
01 = UI 585561 (bar/°F)
02 = UI 585520
Pr 20 - 23
Not used
Pr 24
Zones activation
- only when Pr=01 or 02
- when both zones are required
15
0 … 30min
Pr 25
45
Pr 26
80
K4G2S24ZX version only
Pr 27
Heating temperature MIN
25
25 …45°C
Pr 28
Service inspections
12
00 (= 0 months) …48 (= 48 months)
service
99 = service alert canceled
Pr 29
HW reverse scanning
Dependence
(determines)
Pr 01
00 = HW reverse not measured
01 = HW reverse measured
02 = TBD
03 = TBD
04 (=4°C) … 45 (=45 °C) temperature of
HW reverse
Pr 30
Minimum water pressure
10
00 = monitoring only min. water pressure
01 = TBD
02 = TBD
03 = TBD
04 = TBD
05 (=0,5 bar) … 15 (=1,5 bar) water
pressure adjustment
TBD = To Be Determined