Vexve TERMOVAR Series Mounting And Operating Instructions Download Page 3

TERMOVAR LU (EN) 06.12 

 
 

3 (7) 

 
 
 
 
MOUNTING 

 
 
The valve unit is mounted upright either on the right or left hand side of the heating boiler. After pipework the 
thermometers are pressed onto the front side of the unit. 
 
When starting a new heating installation a very common problem is air in the pipe system. For a trouble free system 
the pipework has to be made without air pockets. If this is not possible the system must be fitted with air vents. 
 
The circulation pump should be started at the same time as the firing. The pump also must be stopped soon after the 
fire has gone out so that the remaining hot water in the boiler can self-circulate to the storage tank. Several boilers 
have factory installed thermostats for pump control. If not, a flue gas thermostat (ACASO Art.-Nr. 7100) must be used. 
 

 
Self-circulation 

 
For self-circulation the supply pipe should be connected to the top of the storage tank and the return pipe to the 
bottom. Self-circulation is obtained as soon as the fire and the circulating pump have stopped. The remaining hot water 
will now self-circulate to the storage tank.   
 

 
Service 

 
TERMOVAR is normally servicefree.  The valve unit has three ball valves. All parts can be changed without draining 
the system. 
 

 
 
 
 
 
 
 
FUNCTION
 
 
 
 
 
 
 
1.  Heat up phase

 

 
The circulation pump should be controlled by a thermostat 
that measures flue-gas temperature. The pump will start 
when the boiler is fired up and stop when it has ceased to 
fire. The boiler water is circulating to the loading unit and 
back while the temperature of the boiler is rising.  

 
 
 
 
 
 
 

Summary of Contents for TERMOVAR Series

Page 1: ...TERMOVAR LU EN 06 12 1 7 TERMOVAR LOADING UNIT MOUNTING AND OPERATING INSTRUCTIONS Sizes Rp 25 Rp 32 28 mm With EPP Insulation With Backflow Preventer Without Backflow Preventer ...

Page 2: ...ansferred into the storage tank It also allows self circulation in case of power failure MAIN PARTS 1 Thermally operated loading valve 2 Automatic balancing valve 3 Backflow preventer Model S without 4 Circulation pump 5 Three thermometers 6 Three ball valves 7 Insulation EPP optional Order No 4919 TECHNICAL DATA Voltage 230 VAC 50 Hz Power consumption Pump speed I 45 W Pump speed II 75 W Pump spe...

Page 3: ...al boilers have factory installed thermostats for pump control If not a flue gas thermostat ACASO Art Nr 7100 must be used Self circulation For self circulation the supply pipe should be connected to the top of the storage tank and the return pipe to the bottom Self circulation is obtained as soon as the fire and the circulating pump have stopped The remaining hot water will now self circulate to ...

Page 4: ...f return water into the boiler When the thermostatic element is fully open the balan cing valve is closed and the entire capacity of the pump is used for cooling the boiler and loading the storage tank 3 End phase The thermostat element is fully open The balancing valve is closed This results a maximum cooling of the heating boiler and the storage tank is fully filled with supply water 4 Self circ...

Page 5: ...ELEMENTS Every thermostatic element has a code on the copper body Code on element Opening temperature Fully open 9311 45 C 60 C 8749 55 C 67 C 8743 61 C 73 C 8719 72 C 84 C 1456 80 C 92 C REPLACING THE THERMOSTATIC ELEMENT Turn off the pump Close the three ball valves Open the cover No 22 opposite the pump Take out the element housing and the spring After replacing the element open the three ball ...

Page 6: ...with spring 3 4955 TERMOVAR body 55ºC 10 4911 Element code 9311 45ºC 3 4961 TERMOVAR body 61ºC 10 4912 Element code 8749 55ºC 3 4972 TERMOVAR body 72ºC 10 4913 Element code 8743 61ºC 3 4980 TERMOVAR body 80ºC 10 4914 Element code 8719 72ºC 4 13 18 4918 Sealing 44 x 32 x 2 mm 10 4915 Element code 1456 80ºC 5 11 19 4904 Ball valve Rp 1 x 28 mm 17 4916 Backflow preventer Model S without 5 11 19 4905 ...

Page 7: ...40 0 20 120 100 60 80 60 0 20 40 100 120 80 120 0 40 20 60 80 100 Heating boiler Right hand mounting Storage tank 40 0 20 120 100 60 80 60 0 20 40 100 120 80 120 0 40 20 60 80 100 Storage tank Left hand mounting Heating boiler ...

Reviews: