Introduction

The VETUS extractor fan type VENT is intended for ventilating
the engine room, toilet or kitchen.

Warning

In order to prevent personal injury, the electrical supply
should always be disconnected during installation and main-
tenance.

Never use the fan where the ambient temperature exceeds
70º C (158 degrees F).

Warning

We DO NOT recommend that this extractor fan is used to
supply air to the ship’s engine. Any engine will be able to
supply itself with air, provided the ventilation openings in the
engine room are large enough. When a fan is fitted in the
engine’s air supply duct, the suction of the engine intake will
make the fan run too fast, causing it to overheat.

Operating Instructions

The fan should be switched on for a minimum of 4 minutes and
the engine room checked for vapour before the engine is start-
ed.

NEVER switch the fan on while refuelling.

Engine room ventilation-Installation example

See Drawing 1. In the situation shown in the drawing, the
engine sucks in air for combustion and cooling via the air inlet
grille. The engine room can only be ventilated by the fan when
the engine is stopped.
N.B.: With a DIESEL engine, the air should preferably enter the
engine room low down, and be extracted as high up as possi-
ble.

Important

With a PETROL engine, the air should enter from high up in
the engine room, and be

extracted as low down as possi-

ble

, where it is most likely that vapour will collect. This point

should always be below the top of the engine foundation.
However, the duct opening should not be so low that there is
a risk of bilge water being sucked into the fan.

Installation

Fit the fan in a bulkhead or floor, high enough above the bilge
water level, in a place free from splashes, drips or deck swab-
bing water.

Determine the position of the fitting holes. Use the fan as a
guide. Drill holes for 4.8 mm. (no. 10) screws. Fix the fan with
the screws. Tighten up the screws evenly, but 

not so tight

that

you split the mounting feet.

Ventilation Duct

Fit ventilation ducting with an internal diameter of 76 mm (3”)
which conforms to the following requirements:

- Smooth inside
- Resistant to a temperature of at least 70º C (158 degrees F)
- Resistant to water, oil and fuel
- Resistant to under and over-pressure

Keep the ventilation ducting as short as possible with as few
bends as possible. Keep the radius of any bends as large as
possible.

Fit the duct with a screwing movement to the duct outlet. Fix
ducting with stainless steel hose clamps.

Electrical Connections

Check that the on-board voltage is the same as that stated on
the fan.
Connect the fan as shown in the diagram, see Drawing 2.
Extend the connector wires if required. Use wiring with a mini-
mum core cross-section of 2.5 mm

2

(AWG 14). Fit a 12 Amp (for

12 Volt) or 6 Amp (for 24 Volt) fuse in the + wire.

Technical Data

Motor

: 12 V or 24 V direct current

Speed

: 4,800 rpm

Current

: Max. 8 A for 12 V; 4 A for 24 V

The motor is ‘ignition protected’.
Capacity

: Max. 4 m

3

/min (141 CFM) for 13.6 V

Duct connection

: ø 76 mm (3”) diameter

Weight

: 1.2 kg (2.65 lbs)

Ambient temperature 

: Maximum 70 degrees C 

(158 degrees F)

8.0105

3

Extractor fan type VENT

ENGLISH

for 12 V

Summary of Contents for VENT Series

Page 1: ...ter Ventilateur Aspirant Ventilador Extractor Ventilatore Aspirante Installatie instructies Installation instructions Installationsvorschriften Instructions d installation Instrucciones de instalación Istruzioni per l installazione NEDERLANDS 2 ENGLISH 3 DEUTSCH 4 FRANÇAIS 5 ESPAÑOL 6 ITALIANO 7 ...

Page 2: ...ar het het meest waarschijnlijk is dat er zich dampen zullen verzamelen Dit punt moet altijd lager liggen dan de bovenzijde van de motorfundatie Het mag echter niet gebeuren dat de slangopening zo laag geplaatst is dat bilgewater mogelijk door de ventilator de slang wordt ingezogen Installatie Monteer de ventilator in een schot of vloer voldoende ruim boven het bilgewaterniveau op een plaats vrij ...

Page 3: ...the top of the engine foundation However the duct opening should not be so low that there is a risk of bilge water being sucked into the fan Installation Fit the fan in a bulkhead or floor high enough above the bilge water level in a place free from splashes drips or deck swab bing water Determine the position of the fitting holes Use the fan as a guide Drill holes for 4 8 mm no 10 screws Fix the ...

Page 4: ...er Punkt muß auf jeden Fall immer niedriger lie gen als die Oberseite der Motorunterlage Die Schlauchöffnung darf jedoch nicht so niedrig angebracht werden daß durch den Entlüftungsschlauch Bilgewasser angesaugt wird Installation Den Ventilator in ein Schott oder Bodenteil montieren und zwar weit über dem Bilgewasserniveau an einem Ort der frei von Spritz Tropfwasser oder Deckwaschwasser ist Die S...

Page 5: ...ossible là où la présence d accumulation de vapeurs est la plus vraisemblable Ce point devra toujours être situé plus bas que la partie supérieure de l assise du moteur Veillez toutefois à ce que l orifice du tuyau ne soit pas trop bas et que l eau de cale ne puisse pas pénétrer dans le tuyau par le ventilateur Installation Montez le ventilateur sur une cloison ou au sol en prévoyant suffisamment ...

Page 6: ...onde con mayor probabilidad se pudie ran producir vapores Dicho punto siempre ha de estar por debajo de la parte superior del pie del motor No obstante tampoco puede ubicarse tan bajo el orificio de manguera que el ventilador pudiera aspirar agua de sentina en la man guera Instalación Montar el ventilador en un tabique o suelo a una altura sufi cientemente por encima del nivel del agua de sentina ...

Page 7: ...situato in ogni caso al di sotto del livello superiore della base del motore Non è consentito situare l apertura del tubo così in basso da provocare l immissione nello stesso della miscela acqua olio presente sul fondo Installazione Montare il ventilatore su una parete divisoria o su una superficie orizzontale ad un livello sufficientemente al di sopra di quello di accumulo della miscela acqua oli...

Page 8: ... 4 Black wire 5 Yellow wire 6 Fan 1 Batterie 2 Sicherung 3 Schalter 4 Schwarzes Kabel 5 Gelbes Kabel 6 Entlüfter 1 Batterie 2 Fusible 3 Commutateur 4 Fil noir 5 Fil jaune 6 Ventilateur 1 Batería 2 Fusible 3 Interruptor 4 Hilo negro 5 Hilo amarillo 6 Vendilador 1 Batteria 2 Fusibile 3 Interruttore 4 Filo negro 5 Filo giallo 6 Ventilatore Hoofdafmetingen Overall dimensions Hauptabmessungen Dimension...

Reviews: