Ultrasonic tank management system
Summary of alarm settings
Low alarm
- Off
The low alarm is switched off.
- On
The low alarm is switched on.
- On output 1
The low alarm is switched on and coupled to
alarm output 1, 2, 3 or 4 respectively.
- On output 2
- On output 3
- On output 4
Low level
the option set for low alarm is carried out when the level in the tank
has dropped to below the set low level
High alarm
- Off
The high alarm is switched of.
- On
The high alarm is switched on.
- On output 1
The high alarm is switched on and coupled to
alarm output 1, 2, 3 or 4 respectively.
- On output 2
- On output 3
- On output 4
High level
the option set for high alarm is carried out when the level in the tank
has risen to above the set high level
2.4.7 Setting the alarms
2 alarms can be set for each tank.
Low alarm,
an alarm when the level in the
tank is lower than the value set for
Low
level
.
High alarm
, an alarm when the level in the
tank is higher than the value set for
High
level
.
See the summary below.
Multiple alarms -high/low or on different
tanks- can be coupled to the same alarm
output.
If warning lights or buzzers are connected
to the alarm outputs, these can be set off
by an alarm.