8.4 Basic Pass/Fail Smoke Test
Note:
This test verifies the detector will sense smoke. It does not replace any appropriate
commissioning test. Use the table below to perform this test by using one of the
following devices.
Procedure
Display Module
LCD Programmer
PC Programmer
Isolate the
Detector.
•
Press the Isolate
button located on
the Display.
•
Check the Isolated
indicator lights up.
•
Select Setup by Zone
↵
Zone Number
↵
Detector
↵
Zone Control
↵
Isolate
Start
↵
•
Select Setup by Zone
↵
Zone Number
↵
Detector
↵
Status
↵
and check
the detector is Isolated.
•
Select Device Tree from
the View menu.
•
Select the detector to be
Isolated from the Device
Tree window.
•
Click on the Isolate icon
or Isolate Zone
command from the
Zone menu.
•
View Active Events list
for response to
Isolation.
Inject Smoke
into any one
of the
sampling air
pipes and
observe the
following
events.
•
Scan starts
•
Sounding device on
Detector beeps.
•
Red LEDs on front
panel lights up.
•
Smoke bar graph
indicator lights up
showing smoke
level.
•
2 digit indicator
shows smoke
intensity level when
Smoke Level is
selected.
•
Select Setup by Zone
↵
Zone Number
↵
Detector
↵
Status
↵
and check
the smoke level value.
•
Alarms reported in
Status menu.
•
Sounding device on the
Detector beeps.
•
Smoke alarm displays
on the Active Events
List window.
After the
smoke has
cleared,
Reset the
Detector to
clear the
alarms.
•
Press the Reset
button once to clear
the alarms and
various fault
indicators.
•
Select Setup by Zone
↵
Zone Number
↵
Detector
↵
Zone Control
↵
Reset
Reset
↵
•
Click on the Reset icon
or select the Reset
command from the
Zone menu.
De-Isolate the
detector.
•
Press the Isolate
button once.
•
The Isolated
indicator goes off.
•
Select Setup by Zone
↵
Zone Number
↵
Detector
↵
Zone Control
↵
Isolate
Stop
↵
•
Select Setup by Zone
↵
Zone Number
↵
Detector
↵
Status
↵
and check
the Isolated alarm is
cleared.
•
Select the Device Tree
command from the View
menu.
•
Click on the detector to
be De-Isolated from the
Device Tree window.
•
Click on the De-Isolate
icon or select the De-
Isolate Zone command
from the Zone menu.
•
View Active Events list
for the Isolated alarm to
clear from the list.