5
ORIGINAL INSTRUCTIONS
VES Andover Ltd Eagle Close Chandlers Ford Ind. Est Eastleigh Hampshire SO53 4NF
Tel: 08448 156060 Fax: 02380 261204 E-mail: [email protected] Web: www.ves.co.uk
Acoustic Supply Unit
Installation, Operation and Maintenance Manual
®
Continued
Colourfan acoustic
units are supplied with feet suitable for floor and ceiling mounting,
either by use of drop rod mounting, in either top or bottom orientation, with airflow in the
horizontal plane. For alternative mounting please consult your outline drawing as
supplied with your unit, or refer to VES Customer Services for further information.
Secure drop rods/unit with M10 fixings as shown below
6
. Self-levelling feet are available
for floor mounting, with M10 fixings as per drop rods
7
. If required the unit can be
further secured to the floor via knockout fixings holes on the feet, fixings to be supplied by
others
8
.
Unit mounting detail
Fig.
6 7 8
Installation
4
Important
When hanging units from drop-rods, it is important that the load is evenly spread and that all
feet are used within the support.
Where provided, flanges and spigots should not be used to support the ductwork
connection. Further consideration should be given to the units position and secured into
place as appropriate.
Colourfan acoustic
units with fitted silencers are sectional and handed. It is important that all
sections are joined together securely prior to positioning and installation. Remove and retain
the fixings from the joining bracket. Butt the correct silencer to the unit section ensuring the
unit spigots enter the silencer section fully
9
. This joint should be assembled using self-adhesive
rubber tape at the joints prior to assembly so as to prevent air leakage; replace with similar if
damaged. Finish the assembly by installing the joint fixings through both parts of each joining
bracket and tighten using a 8mm hex key, drawing the sections together evenly
10
.
Section joining detail
Fig.
9
10
Caution
Joining brackets are
NOT
structural and are included as part of the unit sealing only.
When moving assembled units ensure that
ALL
sections are fully supported.
9
10
6
7
8