System Application Guide
SAG582140600
Spec. No. 582140600 (Model 8100
DB
)
Revision E, November 15, 2018
Page 43 of 67
Monitor Unit Ethernet Connection (if required)
The monitor unit provides a Web Interface via an Ethernet connection to a TCP/IP network. This interface can be accessed
locally on a computer or remotely through a network. An Ethernet port is provided on the monitor unit’s top panel (see Figure
14). A second Ethernet port is provided on the IB4 board (see Figure 10 and Figure 15). The Ethernet port located on the
monitor unit’s top panel can ONLY be used to connect a computer directly to the monitor unit. The Ethernet port located on
the IB4 board can be used to connect the monitor unit to your Local Area Network (LAN).
To Monitor Unit
An RJ-45 10BaseT jack is provided on the top panel of the monitor unit for connection to a computer for local access to the
monitor unit’s web pages (see Figure 14).
Note:
Your system has an IB4 board, DO NOT connect your Local Area Network (LAN) to the monitor unit’s top panel
Ethernet port.
Figure 14
To IB4 Board
An RJ-45 10BaseT jack is provided on the IB4 board for connection into a customer's Local Area Network (LAN) for remote
access to the monitor unit’s web pages (see Figure 10 and Figure 15).
Figure 15
M832D
10/100M Ethernet
Port (RJ-45)
10M Ethernet
Port (RJ-45)
LAN Connection
USB-B Port
(factory
connected)
USB-A Port
(not used)
IB4 Board