will be in a power derating mode. The relationship between the output power and input voltage is illustrated in
the following illustration.
Note:
As depicted in the following illustration, the output power will derate from 100% of the rated capacity
as the input voltage drops below 304 VAC, and to 50% of the rated capacity as the input voltage falls
to 260 VAC.
5.1.6
Power Derating Based on Temperature: The Rectifier Module delivers full power when operating at an ambient
temperature of +45
°
C (+113
°
F) or below. Refer to the following illustration to view the relationship between
the output power and the ambient temperature.
Other power rating values are as follows:
•
At an ambient temperature of +50
°
C (+122°F), the power delivered by the Rectifier Module is greater
than 5400W.
•
At an ambient temperature of +55
°
C (+131
°
F), the power delivered by the Rectifier Module is greater
than 4640W.
5.1.7
Regulation (Rectifier Module)
(A)
Voltage Regulation: ≤±1%
(B)
Load Regulation: ≤±0.5%
(C)
Line Regulation: ≤±0.1%
(D)
Overshoot at Startup: ≤±1%
(E)
Dynamic Response (at rated input and output voltage values):
0
20
40
60
80
100
120
250
275
300
325
350
375
400
425
450
475
500
525
550
%
of
m
ax
. out
put
pow
er
Input Voltage (VAC)
Output Power vs. Input Voltage at Tamb < 45 C
0
20
40
60
80
100
120
-40
-30
-20
-10
0
10
20
30
40
50
60
70
80
%
of
out
put
pow
er
Temperature (C)