![Vertiv NetSure 801NL-B System Application Manual Download Page 60](http://html1.mh-extra.com/html/vertiv/netsure-801nl-b/netsure-801nl-b_system-application-manual_1008114060.webp)
Vertiv
™
NetSure
™
-48 VDC Power System
System Application Guide
Spec. No: 582140001
Proprietary and Confidential © 2022 Vertiv Group Corp.
SAG582140001
Model No: 801
NLDB
, 801
NLEB
, 801
NL
-
B
Page 60
Revision T, September 28, 2022
CB1
CB2
CB3
CB4
CB5
CB6
CB7
CB8
CB9
CB10
CB11
CB12
Odd Numbered
Rectifier Mounting
Slots
Even Numbered
Rectifier Mounting
Slots
380/480VAC (List A) or 208VAC (List B)
3 Phase, 50/60Hz
(2 AC Input Feeds,
1 per 12 Rectifier Modules)
Rectifier #1 Mounting Slot
Rectifier #3 Mounting Slot
Rectifier #5 Mounting Slot
Rectifier #7 Mounting Slot
Rectifier #9 Mounting Slot
Rectifier #11 Mounting Slot
Rectifier #13 Mounting Slot
Rectifier #15 Mounting Slot
Rectifier #17 Mounting Slot
Rectifier #19 Mounting Slot
Rectifier #21 Mounting Slot
Rectifier #23 Mounting Slot
Rectifier #2 Mounting Slot
Rectifier #4 Mounting Slot
Rectifier #6 Mounting Slot
Rectifier #8 Mounting Slot
Rectifier #10 Mounting Slot
Rectifier #12 Mounting Slot
Rectifier #14 Mounting Slot
Rectifier #16 Mounting Slot
Rectifier #18 Mounting Slot
Rectifier #20 Mounting Slot
Rectifier #22 Mounting Slot
Rectifier #24 Mounting Slot
Front cover panel
removed in illustration
Front View
Power Bay
C B A
A B C
Top View
Power Bay
Note: Rectifier numbering is for
wiring identification only.
The MCA identifies rectifiers
differently.
Equipment
Grounding
(1/4-20 Studs
on 1" Centers)
AC Input
(3/8-16 Studs
on 1" Centers)
Six (6) 1.125" openings for 3/4" conduit.
Two (2) conduit plates with
2.5", 1.75", and 1.125" knock-outs
for 2", 1.5", and 3/4" conduit.
Six (6) 1.75" openings for 1.5" conduit
(under plate).