System Application Guide
SAG582120600
Spec. No. 582120600 (Model 801DB
NVGB
)
Revision BK, September 27, 2017
Page 9 of 75
LIST DESCRIPTIONS
List Numbers
List 106: Common Equipment, 6-Panel Bay, w/ Advanced Metering
Features
♦
List 106 provides the common equipment for a 6-Distribution Panel BDF/CBB (Battery Distribution Fuse/Circuit Breaker
Bay) with advanced metering.
♦
Configurable for top or bottom feed.
♦
Consists of a 7’H x 26”W x 15”D welded box framework (seismic, zone 4 earthquake compliant).
♦
Includes an Advanced Meter/Alarm Panel that provides the following functions for each panel in the bay: voltage and
current metering and Low Voltage, Power Lost, Overcurrent, and Fuse/Circuit Breaker alarms. Also provided are four (4)
external alarm relay circuits, to which any combination of alarms can be mapped.
♦
Provides four (4) fused auxiliary -48V power outputs (1-1/3A), fused remote (A/B) meter panel inputs, internal/external
sense option, and an Ethernet connection (requires List 170 Ethernet option).
Restrictions
None.
Ordering Notes
1)
and/or List
2)
If List 120 is ordered, order a List
Capacitor Precharge Assembly, if required.
3)
For any open Distribution Panel position, order a List
4)
Order List
Input Feed and Shunt Assembly as required. Each List 143 or 144 provides input terminations and
shunts for both sides.
For top and bottom feed 2-load applications, order one (1) List 143 or 144 and specify top or bottom feed.
For top and bottom feed multi-load applications, order three (3) List 143 or 144 for each Side A/Side B load and specify
top or bottom feed.
List 120 Only: For 3-load side by side applications, order three (3) List 143 or 144, and order three (3) 556103.
List 125 Only: For 3-load side by side applications, order three (3) List 143 or 144, and order three (3) 557256.
5)
If Distribution Panels (per side) are to be paralleled, order a List
Distribution Panel Paralleling Bar. Each List 130
includes two (2) Paralleling Bars (one per side).
6)
Order List
or List
Internal Ground Bars as required, or External Ground Bars (see ACCESSORY DESCRIPTIONS
section) as required.
7)
List 126 provides input lug landing points at the top or bottom (as specified) of the full bay length ground/return busbars.
List 126 internal return bars are rated for 1200 Amps. List
is available to increase that capacity to 2400 Amps and
provide additional cable landing points. Each bay can accommodate (1) List 148. List 148 offers cable termination at the
rear of the bay and the option of a bonding strap.
8)
Order List
Cable Dressing Bars as required.
9)
Order a
Box Framework Extension as required.
10)
Order distribution fuses, circuit breakers, and load lugs as required per
Distribution Devices and Lug Selection
ACCESSORY DESCRIPTIONS.
11)
For Load and Load Return lug-mounting hardware, order
(ship-loose) as required, or order List
12)
Order TVSS Device(s) as required per
Transient Voltage Surge Suppressor (TVSS) Device
DESCRIPTIONS.
13)
Order DC input lugs as required per
DC Input Cable Sizes and Lugs Selection
under
Wiring Notes
in ACCESSORY
DESCRIPTIONS.
14)
Order bay frame grounding lugs as required per
Bay Frame Grounding Wire Sizes and Lugs Selection
Wiring Notes
in ACCESSORY DESCRIPTIONS.
15)
For remote access capability, order one (1)
Ethernet option.