System Application Guide
SAG582120600
Spec. No. 582120600 (Model 801DB
NVGB
)
Revision BK, September 27, 2017
Page 31 of 75
Distribution Devices and Lug Selection
TLS/TPS Fuses/Fuseblocks, TPL Fuses/Fuseblocks, and Lug Selection for Lists 110 and 120
Features
♦
Each fuse installs into the respective fuseblock.
Restrictions
The fuses and fuseblocks specified in this section are for use in Lists
Load should not exceed 80% of device rating.
Distribution Panel capacity is 640A maximum continuous.
TLS/TPS Fuseblock: Maximum lug width is 0.750”.
Maximum wire size is 2 AWG.
TPL Fuseblock:
Maximum lug width is 1.8”.
Maximum wire size is 2/0 AWG.
Ordering Notes
1)
A List 110 has twelve (12) fuse positions and a List 120 has twenty (20) fuse positions. The fuse panel can be populated
with TLS/TPS fuseblocks (requires one [1] fuse position), TPL fuseblocks (requires two [2] fuse positions), or a
combination of TLS/TPS and TPL fuseblocks.
List 110 includes (12) TLS/TPS Fuseblocks P/N 248817100, and List 120 includes (20) TLS/TPS Fuseblocks P/N
248817100. For panels factory configured in a bay, each TPL Fuseblock P/N 516241 ordered replaces (2) P/N 248817100
Fuseblocks. For fuse panels shipped separately, the TLS/TPS fuseblocks are factory installed and if TPL fuseblocks are
required they will have to be installed in the field.
Order fuses and fuseblocks as required per
For each TLS/TPS fuseblock ordered, also order one (1) P/N 248610301 alarm fuse and one (1) P/N 248898700 safety
fuse cover. The alarm fuse and safety fuse cover is provided with a TPL fuseblock.
2)
See
for recommended load lugs.
3)
See
for recommended load distribution wire sizes.
TLS/TPS Fuse
Fuseblock
(P/N 248817100)
Fuse Case
GMT-18/100A Alarm Fuse
(P/N 248610301) and
GMT-X Safety Fuse Cover
(P/N 248898700)
(Both ordered separately)
Lists 110 and 120 TLS/TPS Fuseblock
1/4 -20 swage studs
for installation of customer
provided single hole lugs
Max. Lug Width 0.750".
Max. Wire Size 2 AWG.