6 Chapter 2 Installation Instruction
NetSure 731 A91 Subrack Power System
User Manual
Rubber ring top cover for MFU unit cabling :
Use the electrician knife incise the "
十
" mark on the rubber unit. As shown in Figure 2-4. Cabling from the cable outlet
area and then fixed to the cable--bunding plate and the top edge by using cable ties.
Lates unit
Cable outlet area
Figure 2-4 Cable entry illustration of the MFU unit
Cabling from the side of the power system
Use a cross head screwdriver to remove two screws which fix the cabling panel at side of cabling area, then the cable
can be led out from the cabling area, as shown in Figure 2-5.
警告
Warning
When the subrack is installed independently on the outside (not installed in the rack). Using system side outlet. The clearance of
the outlet hole must be sealed after connecting the cable to prevent it from touching the live part of the frame.
Screw Screw
Cable hole
Cable hole
Figure 2-5 Side cabling