Vertiv
|
NetSure™ Site Monitoring Unit Installation & User Manual (UM10010507)
|
Rev. A
10
Table 2:
SM-DU+ Switch Settings (cont’d on next page)
DIP Switch SW1
Reserved
HW
/SW
Shunt
Voltage
Shunt
Current
Description of Status
1
2
3
4
5
6
7
8
NA
OFF
NA
Shunt parameter is set through DIP switch.
ON
Shunt parameter is set through software (note 1).
NA
OFF OFF
NA
Shunt Voltage: 25mV (note 1)
OFF ON
Shunt Voltage: 50mV
ON OFF
Shunt Voltage: 60mV
ON ON
Shunt Voltage: 75mV
NA
OFF OFF OFF Shunt Current: 500 A (note 1)
OFF OFF
ON Shunt Current: 100 A
OFF ON
OFF Shunt Current: 200 A
OFF ON
ON Shunt Current: 300 A
ON OFF OFF Shunt Current: 400 A
ON OFF
ON Shunt Current: 1000 A
ON
ON
OFF Shunt Current: 1500 A
ON
ON
ON Shunt Current: 2000 A
Note 1: Default Setting