Junction Cabinet Parameters
Value
500 – 750kVA Attached
Stand-Alone
800 – 1100kVA Attached
Battery Specifications
Nominal Battery Bus, VDC
480V
Battery Float Voltage, VDC
540V
Minimum EOD Voltage, VDC
384V (for VRLA / Flooded Lead Acid)
Physical Parameters
Width, in (mm)
1
15.5 (393)
30.9 (785)
17.5 (445)
Depth, in (mm)
2
33.5 (850)
33.5 (850)
33.5 (850)
Height, in (mm)
76.8 (1950)
76.8 (1950)
76.8 (1950)
Weight, lb (kg) approx.
255 (115)
400 (180)
255 (115)
Color
Black (ZP-7021)
Degree of Protection for UPS Enclosure
IP 20
Minimum clearance, Top
24" (610mm)
Minimum clearance, Back
0"
Minimum clearance, Sides
0"
Location of cable entrance
Top or Bottom
Standards and Conformities
UL 1778; CSA 22.2 107.3; FCC Part 15, Class A
ISTA Procedure 1H; WEEE; IBC 2012/CBC 2010
Environmental
Storage Temperature Range, °F (°C)
-13°F to 158°F (-25°C to 70°C)
Operating Temperature Range, °F (°C)
32°F to 104°F (0 to 40°C)
Relative Humidity
Maximum 95% Non-Condensing
(Operating and Non-Operating)
Maximum Altitude above MSL, ft (m)
4920 (1500) (as per IEC 62040/3) -
1% maximum kW derate / 330ft rise between 4900-9800ft. (100m rise between 1500-3000m)
1.
Width dimensions are with side panels attached. Subtract 1.4 in. (35 mm) for dimensions without side panels.
2.
Depth dimensions include the front door and rear panel.
Table 4.2 Liebert Junction Cabinet Specifications
Electrical Data
Value
Input Voltage
115VAC ±10%
Input Current
3.6A
Frequency
50-60Hz
Table 4.3 Alber Monitoring (Option) Electrical Data
4 Specifications
31
Summary of Contents for Liebert
Page 1: ...Liebert Large UPS Battery System Installer User Guide ...
Page 4: ...Vertiv Liebert Large UPS Battery System Installer Guide ii This page intentionally left blank ...
Page 6: ...Vertiv Liebert Large UPS Battery System Installer Guide 2 This page intentionally left blank ...
Page 14: ...Vertiv Liebert Large UPS Battery System Installer Guide 10 This page intentionally left blank ...
Page 39: ...Vertiv Liebert Large UPS Battery System Installer Guide ...