Battery Cabinet Parameters
Values
Top-Terminal Cabinet
Front-Terminal Cabinet
Operating Temperature Range
32°F to 104°F (0 to 40°C)
74°F to 80°F (23-27°C) for optimal battery life
Relative Humidity
Up to 95% Non-Condensing
(Operating and Non-Operating)
Maximum Altitude Above MSL
4920ft. (1500m) (as per IEC 62040/3) -
1% Maximum kW derate / 330ft. (100m) rise between 4920-9900 ft. (1500-3000m)
1.
Width dimensions are with side panels attached. Subtract 1.4 in. (35 mm) for dimensions without side panels.
2.
Depth dimensions include the front door and rear panel.
3.
Contact the factory about storage at temperatures outside this range.
Table 4.1 Liebert Battery Cabinet Specifications (continued)