4 COMMUNICATION AND CONTROL WIRING
NOTICE
Communication wiring must be performed in accordance with industry standards. All methods,
wiring and connections must comply with local and national codes.
Communication cables must not be kinked or otherwise damaged during installation. Kinked
cables must be replaced.
Communication cables must be properly supported every four feet (1.2m) or less.
4.1 IGM Communication
Liebert SiteLink-E uses the Information Gathering Module Network protocol to communicate to other
Liebert units over the RS-422 protocol. IGM is a point-to-point protocol, where one device connects
directly to another and only those two devices communicate with each other.
NOTE: If shielded cable is used, connect the shield wire to earth (ground) at the Liebert equipment. Do
not ground the shield at the Liebert SiteLink-E.
Liebert SiteLink-E modules have up to 12 IGM ports, depending on the model. The ports are along the
bottom of the module (see Figure 1.1 on page 5).
4.1.1 Wiring IGM Ports
1. Connect the IGM wiring to the SiteLink-E IGM ports, using the labels above the ports as a guide
(see Figure 4.1 below).
2. If using a four-wire connection, set the jumpers, located behind the terminals, as required for
the protocol to be implemented. A guide is at the lower right corner of the module’s housing.
Figure 4.1 IGM connections
Vertiv
| Liebert® SiteLink-E™ Installation Manual |
13
Summary of Contents for Liebert SiteLink-12E
Page 1: ...Liebert SiteLink E SiteLink 2E SiteLink 4E and SiteLink 12E Installation Manual...
Page 4: ...Vertiv Liebert SiteLink E Installation Manual 4...
Page 6: ...Vertiv Liebert SiteLink E Installation Manual 6 This page intentionally left blank...
Page 9: ...Figure 2 4 Enclosure dimensions Floor mount Vertiv Liebert SiteLink E Installation Manual 9...
Page 10: ...Vertiv Liebert SiteLink E Installation Manual 10 This page intentionally left blank...
Page 20: ...Vertiv Liebert SiteLink E Installation Manual 20 This page intentionally left blank...
Page 25: ......