Liebert® SiteLink-E™

SiteLink-2E, SiteLink-4E, and  SiteLink-12E

Installation Manual

Summary of Contents for Liebert SiteLink-12E

Page 1: ...Liebert SiteLink E SiteLink 2E SiteLink 4E and SiteLink 12E Installation Manual...

Page 2: ...any installation or operational issues with your product check the pertinent section of this manual to see if the issue can be resolved by following outlined procedures Visit https www VertivCo com e...

Page 3: ...4 Communication and Control Wiring 13 4 1 IGM Communication 13 4 1 1 Wiring IGM Ports 13 4 2 RS 485 and ARC156 Wiring Considerations 14 4 3 Wiring for BACnet ARC156 Network 15 4 4 Wiring Port S1 16 4...

Page 4: ...Vertiv Liebert SiteLink E Installation Manual 4...

Page 5: ...t power and communication connections ports and switches NOTE This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These...

Page 6: ...Vertiv Liebert SiteLink E Installation Manual 6 This page intentionally left blank...

Page 7: ...cation must be easily accessible within the allowable cable run distances for communication wiring and have about 2 in 51mm on all sides for wiring and service Refer to the following drawings in Enclo...

Page 8: ...Figure 2 2 Enclosure dimensions overall Figure 2 3 Enclosure dimensions Wall mount Vertiv Liebert SiteLink E Installation Manual 8...

Page 9: ...Figure 2 4 Enclosure dimensions Floor mount Vertiv Liebert SiteLink E Installation Manual 9...

Page 10: ...Vertiv Liebert SiteLink E Installation Manual 10 This page intentionally left blank...

Page 11: ...needed for the modules For example if the transformer is rated for 50VA and two modules each rated at 20VA are connected the power trunk uses a recommended 80 of the transformer s power 20 20 40 3 1 1...

Page 12: ...r input terminals to verify that the voltage is within the operating range of 21 6 26 4 VAC 7 Insert the screw terminal connector into the Liebert SiteLink E s power terminals Figure 3 1 Power connect...

Page 13: ...device connects directly to another and only those two devices communicate with each other NOTE If shielded cable is used connect the shield wire to earth ground at the Liebert equipment Do not groun...

Page 14: ...network with a resistor whose value equals the network s characteristic impedance Some third party manufacturers provide a built in resistor that you enable or disable with a jumper Make sure that on...

Page 15: ...ore beginning to connect wiring for the ARCnet port 2 Check the network communication wiring for shorts and grounds 3 Locate the BACnet terminal location in the upper left corner of the Liebert SiteLi...

Page 16: ...ort must match the baud rate of the third party device The baud rate may be set in the module driver properties in Liebert SiteScan Web See the Integration Guide for the third party protocol 1 Be sure...

Page 17: ...dom should exceed 3 000 ft 914 4m at 9600 baud 1 Be sure that power to the Liebert SiteLink E is Off before beginning to connect wiring 2 Check the communication wiring for shorts and grounds 3 Wire t...

Page 18: ...s on the network segment When connecting the Liebert SiteLink E Port S1 to a third party device that uses RS 232 Liebert recommends using 18 28AWG wiring Most RS 232 cables are not twisted pair but tw...

Page 19: ...itch 4 to Disable Off The DIP switches are at the top of the Liebert SiteLink E module near the battery see Figure 1 1 on page 5 for the DIP switch location and Figure 4 5 on the previous page for set...

Page 20: ...Vertiv Liebert SiteLink E Installation Manual 20 This page intentionally left blank...

Page 21: ...Microprocessor 32 bit Motorola Power PC microprocessor with cache memory Fast Ethernet controller high performance 32 bit communication co processor ARCNET communication co processor and I O expansion...

Page 22: ...default 3000 914 4 for 9600 baud Third party RS 232 Various 50 15 24 RS 485 two wire 3000 914 4 for 9600 baud RS 422 RS 485 four wire BACnet PTP RS 232 9600 bps 19 2 kbps 38 4 kbps default 57 6 kbps 1...

Page 23: ...can turn On and Off between transmissions This makes a two wire connection preferable for many reasons including the fact that two wire networking allows for daisy chaining with no need to designate...

Page 24: ...devices enable their transmitters at the same time these are likely to occur on RS 485 RS 422 networks A master slave protocol has one master and many slaves The slaves are always listening and respo...

Page 25: ......