Vertiv
| Liebert
®
RX
™
Remote Distribution Cabinet User Manual |
10
Figure 4
Input electrical field connection location for units with main panelboard breaker
Ground
Busbar
Neutral
Busbar
Input Ground Connection
5/16-18 x 1.5" Stud
Input Neutral Connection
See Detail A
Input Power Connection
Mechanical Lug for
(2) 3/0-500kCMIL
Distribution Cable Conduit
Plate; 56 knockouts, each Ø 0.875"
for 1/2" conduit and 28 knockouts,
each Ø 1.125" for 3/4" Conduit
84-Pole
Distribution
Panelboard
Distribution Cable
Conduit Plate
84 knockouts, each Ø 0.875"
for 1/2" conduit
Main Input
Circuit Breaker
DETAIL A
RX15002
Rev. 2
Ø 0.563
(14.29mm)
4 Places
0.75"
(19.1mm)
1.75"
(44mm)
0.89" (23mm)
1.22" (31mm)
Summary of Contents for Liebert RX
Page 1: ...Liebert RX Remote Distribution Cabinet User Manual ...