Connecting Battery Cabinet Cables
When more than one string is installed, use the factory-provided cable to connect the battery
cabinets, use the factory-provided cable shown in
, Terminal A of the first string
connects to the UPS. Terminal B of the first string will connect to Terminal A of the second string.
Figure 23 Cables between Liebert ITA2 and battery cabinets
The cable connections between the battery cabinet and the UPS are shown in
1.
Communication Cable
2. Power Cable (UPS to Battery
String 1)
3. Terminal A of Battery
Cabinet 1
4. Terminal A of Battery
Cabinet 1
5. Terminal A of Battery Cabinet 1;
Battery String 2
6. Terminal B of Battery
Cabinet 2;
Battery String 2
CABLES FOR UPS TO ONE BATTERY
CABLES FOR ADDITIONAL BATTERY