UPS Properties section
UPS Communication Type
—sets up the communication interface of the UPS. (e.g., Contact
Closure/RS232/3 phase, etc.) Please refer to the UPS manual to set the correct communication type. Any
incorrect settings will cause disconnection between the UPS and IS-WEBRT3N card. The default setting
is RS232.
Last Battery Replaced Date ( mm/dd/yyyy)
—records the date when the UPS battery was last replaced.
Test Log
Displays the self-test history of the UPS. Use the drop-down menus to select how often the UPS self tests,
the start time of the test and the type of test. Under UPS Data Log, enter the time interval to refresh data
in minutes.
Warning Threshold Value section
Time Out when Connection Lost
—sets a certain period of time before sending a disconnection warning.
When the IS-WEBRT3N card loses contact with the UPS it will send a disconnection warning message
after this certain period of time.
Critical Load (%)
—sets the UPS critical loading (shown as %). The NetAgent will send a warning message
when the UPS is overloaded.
Critical Capacity (%)
—sets the UPS critical capacity (shown as %). The NetAgent will send a warning
message when the UPS capacity is overloaded.
4.3.2 UPS On/Off Schedule
This page is used to schedule On/Off time for the UPS.
This page is used to schedule the UPS for automatic start and shut-down. You can also use the drop-
down menu to configure the UPS to shut down when the selected event occurs.
UPS Action
This section can be used to set default actions based on the UPS condition.
Weekly Schedule section
This section is to set the time to turn the UPS On/Off each day of the week.
Date Schedule section
This page is to set the time to turn on/off the UPS on particular days. (Eg, holidays.) The settings here
override the settings in the Weekly Schedule.
NOTE: The card will send a warning message before a scheduled shutdown. You can configure the
delay time period between when the message is sent and when the scheduled shutdown is started.
Wake on LAN
From this page, you can configure waking a PC that is in the network. The PC can be configured to wake
up after a power restore or when the battery capacity reaches the configured capacity percentage.
NOTE: Ensure the PC supports this functionality and is configured as Enabled under the BIOS.
Vertiv
| Liebert® IS-WEBRT3N™ Card User Manual |
14
Summary of Contents for Liebert IntelliSlot WEBRT3N
Page 1: ...Liebert IntelliSlot WEBRT3N Card User Manual ...
Page 4: ...Vertiv Liebert IS WEBRT3N Card User Manual 4 ...
Page 6: ...Vertiv Liebert IS WEBRT3N Card User Manual 6 This page intentionally left blank ...
Page 8: ...Vertiv Liebert IS WEBRT3N Card User Manual 8 This page intentionally left blank ...
Page 10: ...Vertiv Liebert IS WEBRT3N Card User Manual 10 This page intentionally left blank ...
Page 24: ...Vertiv Liebert IS WEBRT3N Card User Manual 24 This page intentionally left blank ...
Page 26: ...Vertiv Liebert IS WEBRT3N Card User Manual 26 This page intentionally left blank ...
Page 27: ......